Prepare boiler location — codes & checklist, Cgs-4e gas-fired water boiler — boiler manual, Installations must follow these codes – Weil-McLain GOLD CGS-4E User Manual
Page 6: Before locating the boiler, check the following

Part number 550-110-282/1108
6
GOLD
CGs-4E Gas-Fired Water Boiler — Boiler Manual
Prepare boiler location — codes & checklist
1a
Installations must follow these codes:
• Local, state, provincial, and national codes, laws, regulations and ordinances.
• National Fuel Gas Code, ANSI Z223.1–latest edition.
• Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/
ASME CSD-1, when required.
• National Electrical Code.
• For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1 Canadian Electri-
cal Code Part 1 and any local codes.
The CGs-4E boiler gas manifold and controls met safe lighting and
other performance criteria when boiler underwent tests specified
in ANSI Z21.13–latest edition.
Before locating the boiler,
check the following:
• Check for nearby connection to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power
• Check area around boiler.
Remove any combustible materials, gasoline and
other flammable liquids, or other contaminants
.
Failure to keep boiler area clear and free of
combustible materials,
gasoline and other flammable liquids and vapors
can result in
severe personal injury, death or substantial property damage.
• Boiler must be installed so that gas control system components are protected from
dripping or spraying water or rain during operation or service.
• If new boiler will replace existing boiler, check for and correct system problems,
such as:
1. System leaks causing oxygen corrosion or section cracks from hard water
deposits.
2. Incorrectly-sized expansion tank.
3. Lack of antifreeze in boiler water causing system and boiler to freeze and
leak.