CGs-4E Gas-Fired Water Boiler — Boiler Manual

3 System or zone circulator
7 System temperature valves (see instructions to the

left for adjusting valves)

8 Blend temperature gauge
9 Relief valve
10 Automatic air vent (with diaphragm-type expan-

sion tank), or connect to tank fitting (closed-type

expansion tank).

DO NOT use an automatic air vent

when using closed-type expansion tank. It would

allow air to leave the system, causing waterlogging

of the expansion tank.

11 Fill valve
12 Diaphragm-type or bladder-type expansion tank,

if used (For closed-type expansion tank, pipe from

top of air separator to tank fitting as in

Figure 5,

page 15.)

Figure 12

System-bypass piping

Zoning with zone valve or circulators,

return water 130°F or higher.

(Alternative to boiler-bypass piping

Figures 10 and 11, page 21)

Figure 13 Piping refrigeration systems

Water piping — refrigeration systems

Prevent chilled water from entering
boiler

Install boiler so that chilled medium is piped in parallel
with the heating boiler. Use appropriate valves to prevent
chilled medium from entering boiler. See

Figure 13

for

typical installation of balancing valve and check valve.

If boiler is connected to heating coils located in air han-
dling units where they can be exposed to refrigerated
air, use flow control valves or other automatic means to
prevent gravity circulation during cooling cycle.