Troubleshooting

(continued)

Temperature/pressure relief valve lifting or weeping

1 Undersized or missing domestic water side expansion tank?

• Is there a thermal expansion tank installed on the domestic supply piping and is it properly sized?

• A thermal expansion tank is required if the domestic supply piping includes a backflow preventer or pressure reducing

valve.

• Ensure the potable water expansion tank is properly sized according to the water heater volume and supply pressure.
• During long periods when there are no draws from the tank (i.e. overnight), the T&P relief valve may lift or weep due to

thermal expansion, but may function properly during normal periods of tank draws.

2 Faulty domestic water side expansion tank?

• Is the expansion tank defective, water logged or improperly charged?

• Check for failed gaskets or bladders, or a faulty Schraeder valve.
• Use a tire gauge to check the charged pressure of the tank.

3 Faulty T & P relief valve?

• Is the temperature/pressure relief valve functioning properly? Dirt and water deposits can accumulate under the valve seat.

4 High domestic water supply pressure?

• Check the domestic supply pressure entering the water heater.

• If the pressure is over 70 psi it is recommended to install a pressure reducing valve. A thermal expansion tank is required

if a PRV is installed.

• This will prevent any pressure spikes or increases in pressure due to thermal expansion which may cause the T&P valve

to lift or weep.

5 Possible water hammering or pressure spikes?

• Check the domestic system for possible sources of water hammering or pressure spikes.

• Some appliances such as clothes washers and dishwashers utilize fast acting valves which may cause water hammering or

pressure spikes through the domestic water system.

• Install water hammer arrestors as required per the manufacturer’s instructions, or install flexible connectors to isolate the

tank from the domestic system

6 Check boiler operating temperature.

• If the boiler operating temperature is too high, stacking can occur in the water heater raising the domestic water tempera-

ture close to the boiler operating temperature. — Reduce the boiler operating temperature to 180°F. Also follow page 32

suggestions if the problem persists.