Boiler-side piping, Aqua plus, Product manual – Weil-McLain AQUA PLUS GL-E223-ADOC 0311 User Manual

Page 11

background image

AQUA PLUS

indirect

-

fired

water

heaters

— Product Manual

Figure 7

Zoning with circulators — direct-connected system piping

Notes

• Place circulators at begin-

nings of zones. Placing

them at the ends of zones

could result in heating idle

zones.

• Size manifold piping for

total flow of all zone cir-

culators.

• Locate flow / check valves

as close as possible to water

heater boiler side connec-

tions — to reduce heat loss

between cycles.

Wiring

• WMCR zone controller,

optional priority — Fig-

ure 18, page 21.

1. This drawing is conceptual

only. It shows representa-
tive piping components
and layout. Weil-McLain
does not represent that this
drawing meets any partic-
ular mechanical or build-
ing codes. The installer is
responsible for inclusion
of all required safety de-
vices, or other miscella-
neous piping hardware not
shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.

2. See boiler manual for spe-

cific details on installing
the boiler.

GV90+ or Ultra gas boilers

:

Do NoT

apply the drawings in

this manual. Refer only to the

boiler manual.

Recommended flow rate and minimum boiler-side pipe size

Heater

model

GPM

Pipe

size

Heater

model

GPM

Pipe

size

35

8

1”

85

14

1¼” *

45

8

1”

105

14

1¼” *

55

8

1”

Requires 1¼”x1” reducers at water heater

Boiler-side piping

Part number GL-E223-ADOC 0311