Troubleshooting

(continued)

4 Check boiler operating temperatures.

• If possible, increase the boiler operating temperature to 180°F or 200°F.

• Maintain a minimal temperature in the boiler during non-heating seasons.

• A boiler typically has a higher standby loss than the indirect water heater.
• After a long standby period, the colder boiler may absorb the stored energy within the water heater

during the initial call for heat.

5 Check location of flow control devices.

• Lab tests have shown that during long standby periods the boiler piping can act as a thermal siphon and

draw stored heat from the domestic water.
• Locate flow control devices (zone valve, spring check valves...) or heat trap loops in the boiler piping

close to the water heater.

• Insulate all boiler piping to and from the water heater.

6 Check for air in the system; check water heater air vent.

• An air-bound water heater or boiler will not circulate system water properly, resulting in a lack of heat

transfer.

7 Clean the boiler water system.

• A dirty boiler system can cause deposits to form on the water heater coil. This insulates the coil, reducing

the heat transfer.
• Clean the boiler system per the boiler manufacturer’s instructions.

• Install a strainer in the boiler piping on older installations or for systems likely to carry sediment.

Insufficient hot water

(continued)