Water heater maintenance

Boiler water — read and comply with all requirements under

“Boiler water restrictions,” page 3.

Water from opened drain valves, unions and other connec-

tions may be extremely hot. To avoid severe personal injury,

death or substantial property damage:

• Tighten all drain hose connections.
• Direct hot water away from all persons.

ATTENTION USER!

Have the water heater serviced at least once an-

nually

by a qualified service technician.

Follow the

maintenance procedures

below at least

monthly.

Read “Water heater temperature adjustment,” page 24.

Failure to comply with the above can result in severe

personal injury, death or substantial property dam-

age.

MONTHLY maintenance by user

• At least

MoNTHLY

, visually check valves, pipes and fittings for

leaks.

• Check hot water supply at several outlets. Make sure water

temperature is not too hot.

• Call qualified service technician to repair leaks or address

problems.

MONTHLY maintenance by user

• At least MONTHLY, visually check valves, pipes and fittings for leaks.
• Check hot water supply at several outlets. Make sure water temperature

is not too hot.

• Call qualified service technician to repair leaks or address problems.

ANNUAL start-up by qualified service

technician

Obtain an Inspection and service kit (see “Replacement parts,”

page 39) before attempting to perform the annual start-up.

This kit contains items that will usually have to be replaced.

Check water supply temperature at several outlets to ensure

the water temperature is acceptable for intended use and

that all temperature control devices are functioning properly.

Read page 3 and verify that all requirements are met by the

installation.

Perform the following procedures:

Perform any procedures required by local codes.

Verify system pressure both on domestic water and

boiler water sides.

Manually operate T&P relief valve at least once

a year (see Figure 21). This will release some hot

water. Move operating lever to open position for

a few seconds and then move it back, allowing it

to snap closed. After T&P relief valve is operated,

if it continues to release water, close cold water

inlet to water heater immediately. Follow draining

instructions, and replace the T&P relief valve. If

T&P relief valve weeps periodically, it may be due

to thermal expansion. Install an expansion tank if

not already installed.

Follow instructions on circulator to oil it, if oil-

lubricated.

Follow instructions in “Inspect anode and water

heater interior,” page 26.

Check valves, pipes and fittings for leaks.

Check function of all controls and valves (see con-

trol manufacturer’s instructions).

Review homeowner’s maintenance responsibilities

Figure 21

T&P valve operation

Before operating the T&P relief

valve, make sure no one is in front of

or around the T&P relief valve dis-

charge piping. Hot discharge water

can cause severe personal injury or

substantial property damage.

Plugging T&P relief valve or dis-

charge piping can cause excessive

pressure in the water heater, result-

ing in severe personal injury, death

or substantial property damage.

Part number GL-E223-ADOC 0311