beautypg.com

1 setting and operating spring loaded valves, 6 shutdown procedure, 7 routine maintenance – Viking SLAL User Manual

Page 8: 8 integral pressure relief valves

background image

SECTION TSM 288

ISSUE

A

PAGE 8 OF 36

Integral pressure relief valves are normally used to protect the

pump from the effects of increases in system pressure caused,

for example, by a restricted or closed discharge line. In

response to a pressure increase the valve opens and internally

circulates the pumped media within the pump chamber.

When the valve opens, because the volume

of fluid circulating is relatively small, the

temperature of the fluid in the pump chamber

may rise if the pump continues to operate for

an extended period. In severe cases this may

result in temperatures in excess of the pumps

operating limits or vaporisation of the fluid, both

of which should be avoided. For these reasons

when the valve is activated the cause of the

system pressure increase should be eliminated

as continuous operation of the pump with the

valve open is not recommended and may cause

severe damage to the pump.

If the pump on which the valve is installed is to be installed

in either a pressurized system or one incorporating a vessel

under vacuum, the application of the valve should be referred

to Viking Pump or their authorized distributor.
The selection, setting and application of integral relief valves

is influenced by the viscosity and nature of the pumped media,

the pump operating speed and the required pressure relief

setting and mode of operation. For these reasons, and to cover

the diverse range of products, the conditions under which they

are pumped, and application demands, it is not practical to

factory set integral relief valves. The setting of the valve should

be carried out on site under the proposed duty conditions for

which the pump and valve were selected.

Before beginning the relief valve setting procedure

the pump should be installed, (see section 3.4)

with a pressure gauge in the discharge line

adjacent to the pump discharge port.

3.8.1 sETTING aNd OPERaTING

sPRING lOadEd ValVEs

See Figures 10, 11, 12 and 13.

• Remove cover (108). For integral relief valve with manual

lift, see Figure 11; first remove nut (129) and hand wheel

(111).

• Loosen nut (107) using a pry bar in the holes

provided, to relieve spring compression. For

integral relief valve with airlift, see Figure 13,

the air cylinder must be exhausted prior to

unscrewing the nut (107).

• Start pump, refer to section 3.5.
• Screw in nut (107) using pry bar in holes provided until

required pressure relief setting is reached.

NOTE: Care should be taken not to exceed the

lower of either the pumps maximum pressure

rating or the system design pressure.

• Reinstall cover (108). For integral relief valve with manual

lift, see Figure 11; reinstall hand wheel (111) and nut (129).

• The relief valve is now set.

3.6 sHUTdOWN PROCEdURE

After shutting the pump down close both the

suction and discharge valves and ensure that the

necessary safety precautions are taken:
• The prime mover power source has been

isolated.

• If installed, the pneumatically operated integral

relief valve has been depressurized.

• If installed, flushed product seal auxiliary

services have been isolated and de-

pressurized.

• Pump head and piping have been drained and

purged.

3.7 ROUTINE MaINTENaNCE

• SL Series pumps are shipped fully lubricated with a lithium

based extreme pressure lubricant suitable for sealed for

life units.

• For lubricant capacities refer to section 6.4.

3.8 INTEGRal PREssURE RElIEf

ValVEs

See Figures 10, 11, 12, 13, 14, and 15.

Most models in the SL Series series can be supplied with

integral pressure relief valves with both spring and air loaded

versions available. The function of the valves can be further

enhanced with the option of manual or airlift override offering

particular benefits where in-line cleaning is employed. Valves

incorporating this option can be opened to regulate the volume

of the cleaning media within the pump chamber thereby

avoiding the need for manual cleaning or external by-pass.
Where the pump is mounted onto a portable base plate

complete with motor and drive to be used as a mobile set, it

is strongly recommended that a integral pressure relief valve

is installed.
The SL Series integral pressure relief valves available include:
Spring Loaded - see Figure 10, 11, 12, & 13.
Valve can be set to required pressure relief setting.
Spring Loaded with Manual Lift - see Figure 11.
Valve can be set to required pressure relief setting. Manual lift

override can be used to open valve without disturbing pressure

relief setting.
Spring loaded with airlift - see Figure 13.
Valve can be set to required pressure relief setting. Airlift

override, which operates on an air supply of up to 7 Bar (105

psi) depending on pressure relief setting, can be used to open

valve without disturbing pressure relief setting.
Air loaded with airlift - see Figure 14.
Valve, which operates on an air supply of up to 7 Bar (100 psi)

for SLA - E, and 10 Bar (145 psi) for SLF, can be set to required

pressure relief setting. Airlift override, which operates on an air

supply of up to 7 Bar (100 psi) for SLA - E and 10 Bar (145 psi)

for SLF, depending on pressure relief setting, can be used to

open valve without disturbing pressure relief setting.
Air actuated relief valves can be operated remotely and

interfaced with other elements of the system or process

control.

WaRNING

WaRNING

!

!

!

This manual is related to the following products: