– 58 –

FILE NO. SVM-03008

10-5. Judgment of Trouble by Every Symptom

10-5-1. Indoor unit (Including remote contro)

(1) Power is not turned on (Does not operate entirely)


1. Is the supply voltage normal?
2. Is the normal voltage provided to the outdoor unit?
3. Is the crossover cable connected properly?
4. Is the fuse (F01) blown?

NO

Turn off power supply once, and

5 second later, turn it on again.

Is OPERATION lamp flashing?

Is it possible to turn on

power supply by pushing

[START/STOP] button

on remote control?

Is voltage

(DC12 V or 5 V)

indicated on rear of

indoor control

board normal?

Does transmission mark

on remote control flash

normally, and is its signal

transmitted properly?

Is DC310-340 V

supplied to

primary side of

transfer switch?

Are DC15 V, 12 V

and 7 V supplied to

secondary side of

transfer switch?

Are DC15 V, 12 V

and 7 V supplied to

secondary side of

transfeor switch?

Does fan

motor connector

between

1

and

2

short-circuit?

Item by symptoms

Operation

Check Item

Considerable principle cause

Measures

Parts (R01, R04, DB01, C01,

C03, IC01 and T01) are defective.

Remote control is defective.

Refer to (5) Troubleshooting

for remote control .

Turn off breaker once

and turn it on again

after removing motor.

Refer to

or this problem is one step

short of power P.C. board block.

Transfer swith,

IC (IC01) for

power supply or

fan motor is

defective.

Unit operates normally.

Replace main

P.C. board

Replace motor.

Is fuse (F01)

of indoor control

board blown?

Microcomputer

is defective.

NO

NO

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

YES

YES

Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of
damage of the motor.