Toshiba RAS-13UAV-E2 User Manual
Page 28
FILE NO. SVM-03008
– 27 –
Air flow rate
RAS-13UKV-E2
(rps)
HIGH
77
M+
65
MED.
53
L–, L
30
UL, SUL
30
(4) Limit for maximum compressor motor speed
by indoor fan speed
When outdoor temperature sensor detected 32
°
C
or lower, and indoor heat exchanger sensor
detected 17
°
C or lower, the maximum compressor
motor speed is limited by the indoor fan speed.
For example, the compressor motor speed is
limited as described in the table below.
Table 8-2-1
rps : round per second
(5) Louver control
The vertical air flow louvers are automatically set
to horizontal or cool memory position.
When temperature of indoor heat exchanger
becomes 5
°
C or lower by the prevent-freezing
control and the compressor is turned off, the
vertical air flow louvers close once and then return
to the position of previous time.
(6) Discharge temperature control
(Common control to cooling and heating)
The discharge temperature of refrigerant gas from
the compressor is detected by the discharge
temperature sensor, and controls operating
compressor motor speed.
1) Control 1 (A zone) : Normal operation zone
When TD detect value is 98
°
C or lower, the
operation is performed with operating motor
speed instructed by the serial signal.
2) Control 2 (B zone) : Slow-up zone of motor
speed
When TD detect value is 98
°
C or higher,
operating motor speed is slowly up.
3) Control 3 (C zone) : Keep zone
When TD detect value is 105
°
C or higher,
operating motor speed is not changed if raising
operation speed.
4) Control 4 (D zone) : Slow down zone of motor
speed
When TD detect value is 108
°
C or higher,
operating motor speed is slowly down.
5) Control 5 (E zone) : Normal down of motor
speed
When TD detect value is 112
°
C or higher,
operating motor speed is down.
6) Control 6 (F zone) : Operation stop zone
If TD detect value exceeds 117
°
C during
operation, stop the operation immediately.
Then, restart the operation when TD detect
value becomes 105
°
C or lower.
Fig. 8-2-3 Compressor motor speed control
(7) ECO operation control
When the ECO button of the remote control is
pushed, quiet and mild operation is performed by
restraining air flow and operating motor speed.
1) Indoor air flow is controlled between SUL and
L.
2) The set temperature increases 0.5
°
C per 1
hour up to +2
°
C starting from the set
temperature when ECO mode has been
received.
Fig. 8-2-4
Zone
Operation stop zone
Normal down zone
of motor speed
Slow down of
motor speed
Keep zone :
Motor speed is not changed.
Slow-up zone of motor speed
Normal operation zone
F
117
TD
(
°
C)
112
108
105
98
E
D
C
B
A
Release of
motor speed
L
−
UL
SUL
rps
FAN
L
40
35
31
27
22
18
13
OFF
+4.0
TA [
°
C]
+3.5
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
−
0.5
−
1.0
−
2.0