Technicolor - Thomson POWER & CONTROL TS 870 User Manual
Page 6
TS 870 TRANSFER SWITCH
PM062 REV 8 10/01/25
2
Thomson Technology
2.1.1.
EQUIPMENT STORAGE
The transfer switch shall be stored in an environment with a temperature range not
exceeding -4° to +158° Fahrenheit (-20° to +70° Celsius) and a humidity range not
exceeding 5%-95% non-condensing. Before storing, unpack sufficiently to check for
concealed damage. If concealed damage is found, notify the ATS supplier and the
Carrier immediately. Repack with the original, or equivalent packing materials.
Protect from physical damage. Do not stack. Store indoors in a clean, dry, well
ventilated area free of corrosive agents including fumes, salt and concrete/cement
dust. Apply heat as necessary to prevent condensation.
2.1.2.
EQUIPMENT OPERATING
The transfer switch shall be operated in an environment with a temperature range
not exceeding +5° to +122° Fahrenheit (-15° to +50° Celsius) and a humidity range
not exceeding 5%-95% non-condensing.
3.
NOTES TO INSTALLER
DANGER!!!!
Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical
personnel utilizing safe work practices and appropriate Personal Protective
Equipment (PPE). Failure to do so may cause personal injury or death
3.1.
UPSTREAM CIRCUIT PROTECTIVE DEVICES/ELECTRICAL
CONNECTIONS
To ensure satisfactory installation of this equipment be sure to observe "Cable Terminal
Information” regarding power cable connection tightness and "Requirements for Upstream
Circuit Protective Devices" located in this manual.
All mechanical and electrical connections must be checked for tightness prior to placing this
equipment in service to ensure proper operation and to validate applicable warranty
coverage.