General description – Technicolor - Thomson POWER & CONTROL TS 870 User Manual
Page 12
TS 870 TRANSFER SWITCH
PM062 REV 8 10/01/25
8
Thomson Technology
2. The anchoring details shown are recommended according to the seismic
certification; design Engineer may use alternate anchors within the scope of IBC.
3. Wall anchors in concrete; use a typical concrete anchor as necessary.
4. Expansion anchors as shown. To be installed according to manufacturer's
recommendation.
5. The 800-1200A NEMA 3R ATS enclosure may be floor/wall mounted or it may be
free standing (floor mounted only); If free standing it must be a minimum of 12"
(305mm) away from pipes, conduits or other obstructions to allow for sway during a
seismic event.
4.
GENERAL DESCRIPTION
Thomson Technology TS 870 series of Automatic Transfer Switches employ two mechanically
interlocked enclosed contact power switching units and a microprocessor based controller to
automatically transfer system load to a generator supply in the event of a utility supply failure.
System load is then automatically re-transferred back to the utility supply following restoration of
the utility power source to within normal operating limits.
The standard TS 870 series Automatic Transfer Switch is rated for 100% system load and requires
upstream over current protection. The TS 870 Automatic Transfer Switch may be supplied with
optional integral over current protection within the enclosed contact power switching units for
applications such as Service Entrance Rated equipment. Refer to
Section 6
of this manual for
detailed information on over current protection.
The TS 870 series transfer switches use a type TSC 80E microprocessor based controller, which
provides all necessary control functions for fully automatic operation. The TSC 80E controller is
mounted on the door of the transfer switch enclosure and operating status is shown via LED lights.
For further information on the TSC 80E Transfer Controller, refer to separate instruction manual
PM063.
The power switching devices used for the Utility and Generator sources are operated by an
electrically driven motor mechanism in the transfer switch. The transfer switch motor utilizes the
power from the source to which the electrical load is being transferred. The mechanism provides a
positive mechanical interlock to prevent both power switching units from being closed at the same
time, which allows an open transition, “break-before-make” transfer sequence. The TSC 80E