TS 870 TRANSFER SWITCH

PM062 REV 8 10/01/25

32

Thomson Technology

The interconnected system shall be evaluated to ensure compliance with the appropriate

schematic drawings. The proper location of sensors and power cabling shall be

determined. The grounding points of the system shall be verified to determine that ground

paths do not exist that would bypass the sensors. The use of high-voltage testers and

resistance bridges may be required. A simulated fault current is to be generated by a coil

around the sensors. The reaction of the circuit-interrupting device is to be observed for

correct response. The results of the test are to be recorded on the test form provided.