Appendix “b – Technicolor - Thomson POWER & CONTROL TS 870 User Manual
Page 50
APPENDIX “B”
THOMSON TECHNOLOGY
©
INSTRUCTIONS TO CHANGE SYSTEM
VOLTAGE ON TS 870 SERIES TRANSFER
SWITCHES WITH /TSC 80E CONTROLLER
9087A - 198
th
Street, Langley, B.C. Canada V1M 3B1
•
Telephone (604) 888-0110
•
Telefax (604) 888-3370
4.
To change system voltage on a TSC 80E controller, the transfer switch must be
energized to provide control power to the controller to allow software programming. To
change the software setting, follow the procedure below
NOTE:
The TSC 80E controller does not utilize the system voltage jumpers,
which are located on the printed circuit board. Any jumpers on the
printed circuit board will be ignored.
5.
Re-connect “Control Circuit Isolation Plug”
6.
Energize Transfer Switch and follow the programming procedure shown below