CABLE TERMINAL INFORMATION

TERMINAL RATING

CONNECTION TIGHTNESS

(In-lbs)

BASIC MODEL

QTY

PER PHASE

RANGE

TERMINAL

MOUNTING

SCREW

CABLE

CLAMP

TS 87xA-0100

1

#14-1/0

120

50

TS 87xA-0150

1

#2–4/0

120

120

TS 87xA-0200

1

#6–350MCM

150

275

TS 87xA-0250

1

#6–350MCM

150

275

TS 87xA-0400

1

2

2/0–500MCM

72

275

TS 87xA-0600

1

2

2/0–500MCM

72

275

TS 87xA-0800

1

3

2/0–500MCM

110

375

TS 87xA-1200

1

4

4/0–500MCM

375

375

1. Optional terminal ratings are available in some models – Consult Thomson Technology.
2. For other model types not shown, contact Thomson Technology for further information.

16.

REQUIREMENTS FOR UPSTREAM CIRCUIT PROTECTIVE DEVICES

16.1. WITHSTAND CURRENT RATINGS (

ALL MODELS WITHOUT INTEGRAL

OVERCURRENT PROTECTION OPTION)

WITHSTAND CURRENT RATING AMPS (RMS)

1

With Upstream Circuit Breaker Protection

With Upstream Fuse Protection

BASIC MODEL

MAX.

VOLTAGE

RATED

CURRENT

(A)

@240V

@480V

@600V

@ Up to 600V

Fuse Type

TS87xA-0100

600

100

65,000

25,000

18,000

100,000

T, J

TS87xA-0150

600

150

65,000

25,000

18,000

100,000

T, J

TS87xA-0200

240

200

65,000

N/A

N/A

N/A

T, J

TS87xA-0250

600

250

65,000

35,000

25,000

100,000

T, J

TS87xA-0400

600

400

65,000

50,000

35,000

100,000

T, J

TS87xA-0600

600

600

65,000

50,000

35,000

100,000

T, J

TS87xA-0800

600

800

65,000

50,000

35,000

100,000

Consult Factory

TS87A-1000/1200

600

1000/1200

65,000

50,000

42,000

100,000

Consult Factory

1.

Standard ratings only are shown. Consult Thomson Technology for versions with higher withstand current ratings.

2.

For other model types not shown, contact Thomson Technology for further information.

Fuse ratings shown are maximum allowable to permit use of the transfer switch in application with

available fault current not exceeding that shown. Consideration must be given to fuse sizing when

fuses also provide overload protection.