TS 870 TRANSFER SWITCH

PM062 REV 8 10/01/25

14

Thomson Technology

5.2.4. ADDITIONAL PROCEDURES

If the "Service Disconnected" pilot light is not illuminated, the service will not

have been successfully disconnected and therefore it is not safe to perform

any maintenance until the following additional procedures are performed

:

DANGER!!!!

Arc Flash and Shock Hazard. Will cause severe injury or death.

Do not open equipment until ALL power sources are disconnected

This equipment must be installed and serviced only by qualified electrical

personnel utilizing safe work practices and appropriate Personal Protective

Equipment (PPE). Failure to do so may cause personal injury or death

1. Open the door to the transfer switch using a suitable tool and opening the

door lock with the key.

2. Visually inspect the actual position of the transfer switch mechanism. If

the position of the transfer switch mechanism is clearly in the "neutral

position" and the load bus is de-energized on all phases, the service has

been successfully disconnected. Proceed to Step. 4.

If the position of the transfer switch mechanism is not in the neutral position

or the load bus is energized, further procedures are required.

Note: If the position of the transfer switch mechanism is clearly in the

"neutral position, the "service disconnected" pilot light may not have

illuminated due to the following reasons:

a) Utility and generator supply voltages are not present (the pilot light

requires AC supply voltage to be present).

b) The pilot light may be burnt out. The bulb should be immediately

replaced with a suitably rated bulb.

c) Failure of one or more of the sensing/logic contacts. A qualified

service technician is required to trouble shoot this specific condition.

Switch the utility control circuit isolation switch to the de-energized

position to remove utility control power. To isolate the generator supply,

remove the control circuit isolation plug. Note: The AC power