Troubleshooting – Technicolor - Thomson POWER & CONTROL TS 870 User Manual
Page 37
TS 870 TRANSFER SWITCH
PM062 REV 8 10/01/25
33
Thomson Technology
18.
TROUBLESHOOTING
DANGER!!!!
Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical
personnel utilizing safe work practices and appropriate Personal Protective
Equipment (PPE). Failure to do so may cause personal injury or death
Symptom
Possible Causes
Will not re-transfer to utility source
upon restoration
- Isolation plug out
- Utility disconnect switch is in the de-energized position
(Service Entrance Rated ATS). Switch to the Energized
position.
- A test mode has been activated (check TSC 80E status LED)
- Utility voltage is below the pre-programmed limits (check utility
source for adequate voltage)
- A loose control connection
- Faulty motor limit switch
- Defective motor
- TSC 80E has incorrect voltage setting as set via software
programming
- Defective TSC 80E controller (verify output signals with circuit
board mounted diagnostic LED’s)
- TSC 80E has “Transfer Fail” alarm activated as indicated by
flashing Load on Utility LED. Determine cause of alarm and
rectify before TSC 80E is reset
Will not transfer to generator source
upon failure of utility source
- Isolation plug out
- Generator set not producing enough voltage/frequency or
output circuit breaker
open
- TSC 80E has incorrect voltage setting as set via software
programming
- Warm-up time delay function has not timed out yet (verify
TSC 80E timer setting)
- A loose control connection
- Faulty motor limit switch
- Defective motor
- Defective TSC 80E controller (verify output signals with circuit
board mounted diagnostic LED’s)
- TSC 80E has “Transfer Fail” alarm activated as indicated by
flashing Load on Generator LED. Determine cause of alarm
and rectify before TSC 80E is reset