Block distinction

Operation of diagnosis function

Check

code

Block

Check

code

Cause of operation

Air

conditioner

status

Display

flashing error

Compressor does not rotate.

All OFF

Flashes after

1. Remove connecting lead wire of the

Because of missed wiring,

error is detected

compressor, and operate again.

missed phase or shortage.

4 times*.

2. If outdoor fan does not operate or

operation but stop after some period,

replace the inverter P.C. board.

3. If outdoor fan operates normally,

measure 3-Phase output of inverter

P.C. board (150-270VAC) at the

connecting lead wire of compressor.

4. If 3-Phase output is abnormal, replace

inverter P.C.Board.

5. If 3-Phase output is normal, measure

resistance of compressor winding.

6. If winding is shortage, replace the

compressor.

Discharge temperature

All OFF

Flashes after

1. Check sensors TD.

exceeded 117

o

C.

error is detected

2. Check refrigerant amount.

4 times*.

3. Check P.M.V. by measure the

resistance of the coil and confirm its

operation (sound of initial

operation, etc.)

4. Observe any possibility cause which

may affect high temperature of

compressor.

Compressor is high current

All OFF

Flashes after

1. Check installation conditions such as

though operation Hz is

error is detected

packed valve opening, refrigerant

decreased to minimum limit.

4 times*.

amount and power supply (rate +10%,

Installation problem.

both of operation and non operation

Instantaneous power

condition).

failure.

2. Check P.M.V. by measure the

Refrigeration cycle

resistance of the coil and confirm its

problem.

operation (sound of initial

Compressor break down.

operation, etc.)

3. Observe any possibility cause which

may affect high current of compressor.

4. If 1, 2 and 3 are normal, replace

compressor.

* 4 times ; When first error is detected, error is count as 1 time, then once operation is stop and re-started.

After re-starting operation within 6 minutes, if same error is detected, error count is add (count become 2 times)

When error count comes 4 times, record error to check code. But after re-starting operation, if no error is

detected and air conditioner can operate more than 6 minutes, error count is cleared.

Action and Judgment

FILE NO. SVM-10020

– 75 –