Item

13. Self-Cleaning

function

Operation flow and applicable data, etc.

Self-Cleaning diagram

Description

Operation display

ON

OFF

OFF

FCU fan

ON ON

OFF

rpm is depend on presetting. (500RPM)

FCU louver OPEN

OPEN (12.7º)

CLOSE

Timer display

ON or OFF

ON

ON or OFF

depend on presetting of timer function.

depend on presetting of timer function.

Compressor

ON or OFF

OFF

OFF

depend on presetting per room temperature.

CDU fan

ON or OFF

OFF

OFF

depend on presetting per room temperature.

Cool mode or dry mode

operation more than 10 mins.

Self-Cleaning mode

operate 30 mins.

Automatically turn-off.

Operation time

Turn off by remote controller or

timer-off function.

41

FILE NO. SVM-10020

How to Set or Cancel Self-Cleaning operation.

(Default setting from factory is ON)

1. Connect jumper lead at J201 of the indoor P.C. board

assembly.

2. To cancel Self-Cleaning operation.

3. To set Self-Cleaning operation.

Turn the power supply ON

Press the [RESET] button located on the front

panel of the indoor unit for more than 3 seconds.

After 3 seconds, the unit beeps three times.

The Self-Cleaning is cancelled.

Turn the power supply ON

Press the [RESET] button located on the front

panel of the indoor unit for more than 3 seconds.

After 3 seconds, the unit beeps three times

and the indicator blinks for 5 seconds.

The Self-Cleaning is set.

One J201 is added, it will effect

as following.

The operation when press

the RESET button for

3 seconds will be changed

from Set/Cancel the

AUTO-RESTART to

Set/Cancel the

Self-Cleaning.

AUTO-RESTART function

will not activate. In case of

AUTO-RESTART is need,

disconnect the jumper

J201 and set it again after

Set/Cancel the

Self-Cleaning finished.

Note :

J201 is near the MCU, so

so take steps to ensure

that it will not be exposed

to excessive of heat.

Also take care to avoid

solder bridging with the

surrounding components.