FILE NO. SVM-10020

Block distinction

Operation of diagnosis function

Check

code

Block

Check

code

Cause of operation

Air

conditioner

status

Display flashing

error

Serial signal

1) Defective wiring of the

Indoor unit

Flashes when

1) to 3) The outdoor unit never

and connecting

connecting cable or

operates

error is detected.

operate.

cable.

miss-wiring.

continue.

Flashing stop

Check connecting cable and correct

2) Operation signal has not

Outdoor unit

and outdoor unit

if defective wiring.

send from the indoor unit

stop.

start to operate

Check 25A fuse of inverter P.C. board.

when operation start.

when the return

Check 3.15A fuse of inverter

3) Outdoor unit has not

signal from the

P.C. board.

send return signal to the

outdoor unit is

Check operation signal of the indoor

indoor unit when operation

normal.

unit by using diode. Measure voltage

started.

at terminal block of the indoor unit

4) Return signal from the between No.2 and No.3 (or L2 and S)

outdoor unit is stop during

If signal is varied 15-60V continuously,

operation.

replace inverter P.C. board.

Some protector

If signal is not varied, replace indoor

(hardware, if exist) of the

P.C. board.

outdoor unit open

4) The outdoor unit abnormal stop at

circuit of signal.

some time.

Signal circuit of indoor

If the other check codes are found

P.C. board or outdoor

concurrently, check them together.

P.C. board is failure

Check protector (hardware) such

in some period.

as Hi-Pressure switch,

Thermal-Relay, etc.

Check refrigerant amount or any

possibility case which may caused

high temperature or high pressure.

Check operation signal of the indoor

unit by using diode. Measure voltage

at terminal block of the indoor unit

between No.2 and No.3 (or L2 and S)

If signal is varied 15-60V continuously,

replace inverter P.C. board.

If signal is not varied, replace indoor

P.C. board.

Action and Judgment

* Signal send only 1 minute and stop. Because of return signal from outdoor unit has not received.

** Signal resend again after 3 minutes stop. And the signal will send continuously.
*** 1 minute after resending, the indoor unit display flashes error.

VDC

Time (Min)

0

3

4

7

8

15

60

M

ea

su

re

d s

ign

al

v

olt

age

by

a

pply

dio

de

3 minutes Delay, start
counting from power
supply ON or remote
OFF.

3 minutes stop

*

**

***

Sending signal of the indoor unit when have not return

signal from the outdoor unit.

Voltage variation stop
or have not voltage
output.

Note :

Operation signal of the indoor unit shall be measured in the sending period as

picture below.

– 72 –