2. operation data – Toshiba CARRIER RAS-15LKV-UL User Manual
Page 23
7-2. Operation Data
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition [°F (°C)] RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P [psi (MPa)] T1 [°F (°C)] T2 [°F (°C)] (rps)
80/67
98/75
131 to 160
52 to 55
40 to 42
(26.7/19.4)
(35/23.9)
(0.9 to 1.1)
(11 to 13)
(37 to 39)
131 to 160
52 to 55
40 to 42
(0.9 to 1.1)
(11 to 13)
(42 to 44)
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
RAS- pressure pipe temp. fan mode fan mode revolution
Indoor
Outdoor
(rps)
70/60
47/43
363 to 392
102 to 105
32 to 37
(21.1/15.6)
(8.3/6.1)
(2.5 to 2.7)
(39 to 41)
(0 to 3)
377 to 406
106 to 106
32 to 36
(2.6 to 2.8)
(41 to 43)
(0 to 2)
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 25 ft (7.5m)
74
High
High
82
15LKV-UL
17LKV-UL
High
High
17LKV-UL
High
High
62
High
High
57
15LKV-UL
131 to 160
52 to 55
41 to 43
(0.9 to 1.1)
(11 to 13)
(42 to 44)
22LKV-UL
High
High
88
116 to 145
52 to 55
104 to 107
(0.8 to 1.0)
(11 to 13)
(42 to 44)
22LKV-UL
High
High
84
FILE NO. SVM-10020
– 23 –
condition [°F (°C)]
P [psi (MPa)] T1 [°F (°C)] T2 [°F (°C)]