Item

4. Capacity

control

Operation flow and applicable data, etc.

The cooling or heating capacity depending on the load is
adjusted.

According to difference between the setup value of tempera-
ture and the room temperature, the capacity is adjusted by
the compressor revolution.

Description

1) The difference between set

temperature on remote controller
(Ts) and room temperature (Ta)
is calculated.

2) According to the temperature

difference, the correction value of
Hz signal which determines the
compressor speed is set up.

3) The rotating position and speed

of the motor are detected by the
electromotive force occurred on
the motor winding with operation
of the compressor.

4) According to the difference

resulted from comparison of the
correction value of Hz signal with
the present operation Hz, the
inverter output and the commuta-
tion timing are varied.

5) Change the compressor motor

speed by outputting power to the
compressor.

* The contents of control

operation are same in cooling
operation and heating
operation

This function prevents troubles on the electronic parts of the
compressor driving inverter.

This function also controls drive circuit of the compressor
speed so that electric power of the compressor drive circuit
does not exceed the specified value.

5. Current release

control

Outdoor temp. To

Setup of current release point

Capacity control continues.

Current decrease

Outdoor unit inverter main

circuit control current

High

Low

Reduce compressor speed

Operating current

Setup value

1) The input current of the outdoor

unit is detected in the inverter
section of the outdoor unit.

2) According to the detected

outdoor temperature, the
specified value of the current is
selected.

3) Whether the current value

exceeds the specified value or
not is judged.

4) If the current value exceeds the

specified value, this function
reduces the compressor speed
and controls speed up to the
closest one commanded from the
indoor unit within the range
which does not exceed the
specified value.

Outdoor temp.

Cooling current release value

Heating current release value

RAS-15LAV-UL

RAS-22LAV-UL

113ºF (45ºC)

104ºF (40ºC)

61ºF (16ºC)

52ºF (11ºC)

111ºF (44ºC)

102ºF (39ºC)

60ºF (15.5ºC)

51ºF (10.5ºC)

6.07A

7.12A

8.47A

7.05A

9.30A

10.50A

8.77A

10.88A

FILE NO. SVM-10020

RAS-17LAV-UL

RAS-17LAV-UL

RAS-15LAV-UL

RAS-22LAV-UL

Set temp. (Ts)

Room temp. (Ta)

Correction value of Hz signal

Detection of electromotive force

of compressor motor winding

Inverter output change

Commutation timing change

Change of compressor speed

Remote contr oller

Indoor unit

Ts

−Ta

Correction value of Hz signal- Operating Hz

Detection of motor speed (Operation Hz)

and rotor position