81

Note 3

Note 1

Note 2

Code

indication

Status message

Meaning

Guidance

Buzzer

External

relay contact

Failure

lamp

UF301

UPS CONTROL

CIRCUIT ERROR

AD reference has an abnormal value.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF302

UPS CONTROL

CIRCUIT ERROR

Detection of an external interruption during

the software execution.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF303

UPS CONTROL

CIRCUIT ERROR

Timer does not reset in the specified period

(WDT settings)

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF305

UPS CONTROL

CIRCUIT ERROR

Detection of an abnormal clock speed in the

DSP or FPGA.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF306

UPS CONTROL

CIRCUIT ERROR

Control power supply voltage is below the

specified level.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF309

INVERTER

VOLTAGE

ABNORMAL

Inverter voltage is out of the specified range. CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF310

CONTROL POWER

SUPPLY

ABNORMAL

MMS backup control power supplies exhibit

abnormal condition.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF320

UPS CONTROL

CIRCUIT ERROR

Cable disconnection in the parallel interface

board during load supply.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF323

UPS CONTROL

CIRCUIT ERROR

Major communication error during parallel

operation.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF331

UPS CONTROL

CIRCUIT ERROR

Gate driver abnormal for phase U (Note 4)

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF332

UPS CONTROL

CIRCUIT ERROR

Gate driver abnormal for phase V (Note 4)

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF333

UPS CONTROL

CIRCUIT ERROR

Gate driver abnormal for phase W (Note 4)

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF334

UPS CONTROL

CIRCUIT ERROR

Gate driver abnormal for chopper (Note 4)

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF352

CONTROL POWER

SUPPLY

ABNORMAL

SMS backup control power supplies exhibit

abnormal.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF363

UPS CONTROL

CIRCUIT ERROR

Synchronization error signal is being

received for a considerable time.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF371

UPS CONTROL

CIRCUIT ERROR

Minor communication error during parallel

operation.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF372

UPS CONTROL

CIRCUIT ERROR

Unable to synchronize the inverter output

and the bypass voltage when the bypass is

normal.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF374

UPS CONTROL

CIRCUIT ERROR

Cable disconnection in the parallel interface

board.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF375

UPS CONTROL

CIRCUIT ERROR

Unable to achieve synchronization for

parallel operation.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF376

UPS CONTROL

CIRCUIT ERROR

No control response from another UPS

although its detection is possible.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF377

UPS CONTROL

CIRCUIT ERROR

Overload detection signal is being received

continuously for a considerable time.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF378

UPS CONTROL

CIRCUIT ERROR

No answer for sending synchronizing signal.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF379

UPS CONTROL

CIRCUIT ERROR

Abnormal clock speed of the parallel control

board processor.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker