TABLE 3.4 Recommended Cable Sizes

Input Side

Output Side

Bypass Side

DC Input Side

kVA

Capacity

Input

Voltage

Output

Voltage

Cable

Size

Torque

ft. lbs

Cable

Size

Torque

ft. lbs

Cable

Size

Torque

ft. lbs

Cable

Size

Torque

ft. lbs

80kVA

480V

480V

1 AWG –
1/0 AWG

17-22

ft. lbs

1 AWG –
1/0 AWG

17-22

ft. lbs

1 AWG –
1/0 AWG

17-22

ft. lbs

3/0 AWG –

4/0 AWG

17-22

ft. lbs

100kVA

480V

480V

2/0 AWG –

3/0 AWG

17-22

ft. lbs

2/0 AWG –

3/0 AWG

17-22

ft. lbs

2/0 AWG –

3/0 AWG

17-22

ft. lbs

(2) x 1 AWG –
(2) x 2/0 AWG

17-22

ft. lbs

160kVA

480V

480V

250 MCM –

300 MCM

17-22

ft. lbs

250 MCM –

300 MCM

17-22

ft. lbs

250 MCM –

300 MCM

17-22

ft. lbs

(2) x 3/0 AWG –

(2) x 250 MCM

17-22

ft. lbs

225kVA

480V

480V

500 MCM –

(2) x 250 MCM

17-22

ft. lbs

500 MCM –

(2) x 250 MCM

17-22

ft. lbs

500 MCM –

(2) x 250 MCM

17-22

ft. lbs

(2) x 350 MCM –

(2) x 400 MCM

17-22

ft. lbs

300kVA

480V

480V

(2) x 250 MCM –

(2) x 300 MCM

29-39

ft. lbs

(2) x 250 MCM –

(2) x 300 MCM

29-39

ft. lbs

(2) x 250 MCM –

(2) x 300 MCM

29-39

ft. lbs

(3) x 300 MCM –

(3) x 350 MCM

29-39

ft. lbs

500kVA

480V

480V

(3) x 300 MCM –

(3) x 350 MCM

29-39

ft. lbs

(3) x 300 MCM –

(3) x 350 MCM

29-39

ft. lbs

(3) x 300 MCM –

(3) x 350 MCM

29-39

ft. lbs

(4) x 500 MCM –

(5) x 300 MCM

29-39

ft. lbs

750kVA

480V

480V

(4) x 350 MCM –

(5) x 250 MCM

29-39

ft. lbs

(4) x 350 MCM –

(5) x 250 MCM

29-39

ft. lbs

(4) x 350 MCM –

(5) x 250 MCM

29-39

ft. lbs

(6) x 400 MCM –

(6) x 500 MCM

29-39

ft. lbs


*1 – The cables must be selected to be equal to the sizes listed in the table.
*2 – Voltage drop across power cables not to exceed 2% of nominal source voltage.
*3 – Allowable ampere-capacities based on 75

°C insulated copper conductor at ambient temperature of 30 °C.

*4 – All wiring to be in accordance with all applicable national and/or local electrical codes.