G9000 Installation and Operation Manual
5
This UPS does not include a Bypass input circuit breaker (MCCB) to protect
the bypass circuit. The Bypass input circuit breaker (MCCB) is to be field
supplied and installed. Recommended Breaker (MCCB)'s Specifications are
as follows:
TABLE 1.2
Rating of Bypass Input Circuit Breaker
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)
Breaker (A)
80
480
96
125
100
480
120
150
160
480
192
250
225
480
271
350
300
480
361
500
500
480
601
800
750
480
902
1200
AC input and AC output overcurrent protection and disconnect devices shall be field
supplied and installed. The DC circuit breaker (MCCB) shall be field supplied and installed.
The overcurrent protection device should be installed in the Battery cabinet and rated as
indicated in TABLE 1.6.
Note: The DC input overcurrent protection (Battery disconnect breaker) hereinafter will be
referred as “CB2”.
WARNING 4
!
NOTE
- Power Inverter (15 pages)
- 1800 (6 pages)
- TOSVERT VF-S11 (68 pages)
- Density (Consistency) Meter LQ500 (9 pages)
- MBSB80-225-43 (1 page)
- TOSNIC-7000S (53 pages)
- 1600EP Series (3 pages)
- 1500 (32 pages)
- TOSVERT VF-FS1 Series (16 pages)
- 4200FA XT1 (1 page)
- G3 Plus Pack (4 pages)
- Tosvert VF-A5 (149 pages)
- 1600 Series (3 pages)
- G9000 (100 pages)
- TEC EO1-33030 (54 pages)
- 1000 Series (2 pages)
- 1500 Plus (31 pages)
- G8000MM (6 pages)
- VT130G1 (99 pages)
- 4200FA Series (2 pages)
- VF-PS1 (10 pages)
- GX7 Series (6 pages)
- 4200FA XT (1 page)
- RMTI-EMD-HT (2 pages)
- W7 Series (6 pages)
- HX7 (6 pages)
- PDP002Z (18 pages)
- RELIABILITY IN MOTION 1700 (39 pages)
- 1700 Series (2 pages)
- G3 TOSVERT-130 (62 pages)
- B-852-TS12-QP (55 pages)
- 1000 (4 pages)
- E3 (7 pages)
- Adjustable Speed Drive H3 (122 pages)
- 55611-001 (2 pages)
- Black Gold Series (2 pages)
- Dura-Bull TX (6 pages)
- Current Relay RC803A-HP1 (19 pages)
- 1800 SERIES (2 pages)
- Isolated-Redundant UPS System (2 pages)
- Tosvert VF-AS1 (312 pages)
- RELIABILITY IN MOTION 1000 (54 pages)
- REMOTE-D (2 pages)
- 15-80KVA (2 pages)