G9000 Installation and Operation Manual

79

Note 3

Note 1

Note 2

Code

indication

Status message

Meaning

Guidance

Buzzer

External

relay contact

Failure

lamp

UF109

DC UNBALANCED

Major unbalance of the neutral point voltage. CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF110

ZERO PHASE

OVERCURRENT

Detection of converter zero-sequence

overcurrent.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF111

UPS CONTROL

CIRCUIT ERROR

Battery current unbalance.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF112

DC CIRCUIT

ABNORMAL

Sudden change of the DC voltage level.

CALL SERVICE

ENGINEER

Continuousso

und

Major

Lit on

UF119

DC GROUND

FAULT

Detection of DC ground fault UF159 exceeds

10 seconds. UPS transfers to bypass.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF128

CONTROL POWER

SUPPLY

ABNORMAL

Power supply voltage to IGBT driver PCB is

below the specified level.

CALL SERVICE

ENGINEER

Continuous

sound

Major

Lit on

UF151

DC VOLTAGE

ABNORMAL

24 hours after input power restoration,

batteries does not reach float voltage level.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF152

DC VOLTAGE

ABNORMAL

Unable to equalize the voltage of various

batteries after 24 hours.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF154

CB2 ABNORMAL

During UVR, status signal from CB2 is ON.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF156

CHG.STOPPED

(BATTERY

OVERTEMP.)

UF157 failure persisted for over 2 hours.

CHECK BATTERY

Intermittent

sound

Minor

Battery

abnormal

Flicker

UF157

BATTERY

OVERTEMPERATU

RE

Detection of overtemperature at the

batteries.

CHECK BATTERY

Intermittent

sound

Minor

Battery

abnormal

Flicker

UF158

BATTERY LIQUID

LOW

Low level of battery electrolyte solution.

CHECK BATTERY

Intermittent

sound

Minor

Battery

abnormal

Flicker

UF159

DC GROUND

FAULT

Detection of DC ground fault. Chopper

operation is stopped.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF160

UPS CONTROL

CIRCUIT ERROR

Abnormal behavior of DC current sensor.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF161

CHG.STOPPED(DC

VOLT. ABNORMAL) UF151 failure is running for over 24 hours.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF162

BATTERY

ABNORMAL

Failure detection based on battery

self-check.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF163

BATTERY

VOLTAGE

ABNORMAL

Battery voltage is abnormal.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF170

VDB SENSOR

ABNORMAL

Detection of a large variation of the

difference between control-only and

protection-only battery voltage.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF171

UPS CONTROL

CIRCUIT ERROR

Poor shared current in parallel chopper

circuit; or improper charging current.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker

UF172

CHG. STOPPED

(DEVICE STATUS)

Energy storage device error.

CALL SERVICE

ENGINEER

Intermittent

sound

Minor

Flicker