ACTION TYPE SUBMENU:
The error that results from the measurement of the Process Variable may be
positive or negative since it may be greater or smaller than the Setpoint. If a
positive error should cause the instrument output to increase (i.e. cooling), it
would be called Direct Acting. If a negative error should cause the output to
decrease (i.e. heating), it would be called Reverse Acting.
Press
d
6) Display flashes
DRçT Direct or RVRS Reverse.
Press
b
7) Scroll through the available selections: “Direct” or “Reverse”.
Press
d
8) Display shows
STRD stored message momentarily and then
advances to
AUTo only, if it was changed, otherwise press a to
advance to
AUTo Auto PID Submenu (If PID Control type was
selected).
If ON/OFF was selected in the Control Type, the display skips to
the Dead Band Submenu.
AUTO PID SUBMENU:
Press
d
9) Display flashes
ENBL Enable or DSBL Disable.
Press
b
10) Scroll through the available selections: “Enable” or “Disable”.
If "Enabled", the PID parameter of Output 1 will be copied to
Output 2.
Press
d
11) Display shows
STRD stored message momentarily and then
advances to the next submenu only, if it was changed, otherwise
press
a to advance to the next submenu.
If AUTO PID was ENABLED", the display skips to the
CYCL
CYCLE TIME submenu. If "AUTO PID" was "DISABLED", the
display will show
PRoP PROPORTIONAL BAND Submenu
allowing the user to manually enter the Proportional Band value.
The Reset and Rate value are the same as Output 1.
PROPORTIONAL BAND SUBMENU:
Press
d
12) Display flashes 1
st
digit of the previous Proportional Band
value.
Press
b & c 13) Press b and c buttons to enter a new Proportional Band
value.
Press
d
14) Display shows
STRD stored message momentarily and then
advances to
CYCL only, if it was changed, otherwise press a to
advance to the
CYCL Cycle Time Submenu.
Refer to “Proportional Band” Submenu of “Output 1” Menu.