20
Input Type (RTD)
ENTER INPUT TYPE MENU:
Press
a
1) Press
a, if necessary, until CNFG prompt appears.
Press
d
2) Display advances to
INPT Input Menu.
Press
d
3) Display flashes
T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is
RTD, press a to skip to
step 6 (
RTD stops flashing).
RTD SUBMENU:
Press
b
4) Scroll through the available selection to
RTD (flashing).
Press
d
5) Display shows
STRD stored message momentarily and then
RTD (not flashing).
Press
d
6) Display flashes previous RTD type selection i.e.
392.2
(see below for RTD types selection).
Press
b
7) Scroll through the available RTD types to the selection of
your choice.
Press
d
8) Display shows
STRD stored message momentarily and then
advances to
RTD RTD value.
RTD Types: 392 385 Two, Three or Four-wire
Display:
392.2, 392.3, 392.4, 385.2, 385.3, 385.4
Last digit indicates: 2-, 3- or 4-wire input.
RTD VALUE SUBMENU:
Press
d
9) Display flashes previous RTD value selection i.e.
100_
(see below for RTD value selection).
Press
b
10) Scroll through the available RTD values to the selection of
your choice.
Press
d
11) Display shows
STRD stored message momentarily and then
advances to
RDG Reading Configuration Menu.
RTD Values: 100 ohm
500 ohm
1000 ohm
Display:
100_
500_
1000