Omega ILD44-UTP User Manual
Page 31
27
CONTACT CLOSURE SUBMENU:
Press
d
11) Display flashes previous selection. Press
b to N.ç. Normally
Closed or
N.o. Normally Open.
Press
d
12) Display shows
STRD stored message momentarily and then
advances to
AçTV only if it was changed, otherwise press a to
advance to
AçTV Active Submenu.
Normally Open: If this feature is selected, then the relay is "energized" only
when an alarm condition occurs.
Normally Closed: "Fail Safe" Mode. Relay is energized under "normal"
conditions and becomes de-energized during alarm or power failure.
ACTIVE SUBMENU:
Press
d
13) Display flashes previous selection. Press
b to scroll through
the available selections:
ABoV Above, BELo Below, HI.Lo
HI/Low and
BAND Band. (Band is active if _DEV Deviation was
selected).
Press
d
14) Display shows
STRD stored message momentarily and then
advances to
A.P.oN only if it was changed, otherwise press a to
advance to
A.P.oN Alarm Enable/Disable at Power On Submenu.
Above: Alarm 1 condition triggered when the process variable is greater than the
Alarm Hi Value (Low value ignored).
Below: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).
Hi/Low: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.
Band: Alarm 1 condition triggered when the process variable is above or below
the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.