3.2.11 Output 2
Output 2 and Alarm 2 share the same contacts on the rear panel connector. If
Alarm 2 is Enabled, Output 2 is automatically Disabled.
Figure 3.10 Flow Chart for Output 2
ENTER OUTPUT 2 MENU:
Press
a
1) Press
a, if necessary, until CNFG prompt appears.
Press
d
2) Display advances to
INPT Input Menu.
Press
a
3) Press
a, if necessary, until Display advances to OUT2
Output 2 Menu.
Press
d
4) Display advances to
CTRL Control Type Submenu.
CONTROL TYPE SUBMENU:
Press
d
3) Display flashes
ON.OF ON/OFF, or PID PID.
Press
b
4) Scroll through the available selections: “ON/OFF” or “PID”.
Press
d
5) Display shows
STRD stored message momentarily and then
advances to
AçTN only, if it was changed, otherwise press a to
advance to
AçTN Action Type Submenu.
The ON/OFF control is a coarse way of controlling the Process. The “Dead
Band” improves the cycling associated with the ON/Off control. The PID control
is best for processes where the Setpoint is continuously changing and/or tight
control of the Process Variable is required.
It is recommended that you put the
controller in the Standby Mode for any
configuration change other than
Setpoints & Alarms.