beautypg.com

Access control – Omega Speaker Systems Dual Thermocouple Over the Internet iSE-TC User Manual

Page 22

background image

18

4.2 Setting a New IP Address over the Network

Besides using the iConnect software, you may use the iSE’s default IP address to

access it and assign a new IP address to it.

The iSE is shipped with a default IP address of 192.168.1.200 and Subnet Mask of

255.255.255.0. You can configure your PC’s Network connection with an IP address that

is in the same range as the iSE’s IP address (192.168.1.x) and connect to the iSE using a

crossover network cable between your PC and the iSE.

With this completed, you can go to the DOS-Prompt and ping 192.168.1.200. If you

receive responses back (Figure 4.1), you can go to a Web browser and type in

http://192.168.1.200 and it will take you to the iSE’s main web page.

Select

, button, you’ll be asked for the password. The default LOGIN

password is "12345678" and the ADMINISTRATOR password is "00000000", then you

should be on the Access Control page were you can simply type in the desired Static IP

address, and click Save.

Figure 4.4 Access Control

For the IP address to take effect, the iSE needs to be turned OFF/ON. Clicking the

“Power Recycle” button will turn the iSE OFF and ON. Pressing the physical button

marked “RESET” on the iSE does the same thing.

You can now connect the iSE to an Ethernet hub using a straight through cable, power it

up, and follow the ping routine mentioned in the previous section.

ACCESS CONTROL

ACCESS CONTROL

http://192.168.1.200

Address

Main Menu

Login Password: 12345678

Admin Password: 00000000

IP Address: 192.168.1.200

Camera IP: 0.0.0.0

Gateway Address: 0.0.0.0

Camera Label:

Camera Location

Subnet Mask: 255.255.255.0

MAC Address: 00:03:03:00:21:D9

Host Name: eis21d9

Save Reset

Power Recycle

Access Control

Click the following button to activate the new settings.