MATE SCREENS
CALIBRATION MENU
The CAL
(calibration) section is used in the factory or field to make fine adjustments in the operation of the FX. It is particularly useful
when multiple FX’s are connected together in the different stacking configurations to maximize the performance of the FX’s.
In most cases, the user will not need to adjust these settings from the factory default values.
ADV/FX/PAGE1--------
choose category:
ADV
INV
CHGR
PG2
↓
ADV/FX/PAGE2--------
choose category:
PG1
GRID
GEN
PG3
↓
ADV/FX/PAGE3--------
choose category:
PG2
AUX
STACK
PG4
↓
ADV/FX/PAGE4--------
choose category:
PG3
SELL
CAL
MAIN
↓
ADV/FX/CALIBRATE-P00
vac input
120 vac
adjustment
DOWN
INC
DEC
PORT
↓
ADV/FX/CALIBRATE-P00
vac output
120 vac
adjustment
DOWN
INC
DEC
PORT
↓
ADV/FX/CALIBRATE-P00
battery vdc 12.8 vdc
adjustment
DOWN
INC
DEC
PORT
↓
ADV/FX/CALIBRATION--
calibration setup
completed
TOP
ADV
MAIN
Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is
displayed. Selecting
Selecting
Selecting
Selecting
The VAC INPUT ADJUSTMENT allows calibration of the AC input voltage. If the AC source is
measured and is different than the value read from the MATE, the user can adjust it to match the
measured value. This value can be raised by pressing the INC button. Conversely, this value can
be lowered by pressing the DEC button. The value can be raised or lowered up to 2 vac.
The VAC OUTPUT ADJUSTMENT allows calibration of the AC output voltage. If the AC output is
measured and is different than the value read from the MATE, the user can adjust the reading to
match the measured value. This value can be raised up to 2 vac by pressing the INC button and
lowered up to 2 vac by pressing the DEC button. NOTE: This only affects the MATE's voltage
display - See page 51 [ADJ. OUTPUT VOLTAGE] for actual adjustment of inverter VAC output.
The BATTERY VDC ADJUSTMENT allows calibration of the battery voltage. If the battery voltage
is measured and is different than the value read from the MATE, the user can adjust it to match the
measured value. This value can be raised by pressing the INC button. Conversely, this value can
be lowered by pressing the DEC button. The value can be raised or lowered up to 0.2 vdc for 12V
battery system, 0.4V for 24V battery systems, and 0.8V for 48Vbattery systems.
Selecting TOP returns the user to the top of the ADV/FX/CALIBRATION menu section. Selecting
ADV returns you to the advanced screen to allow selection of another product connected to the
MATE. Selecting MAIN returns the display to the MAIN screen.
END OF ADVANCED MENU SYSTEM