MATE SCREENS

CALIBRATION MENU

The CAL

(calibration) section is used in the factory or field to make fine adjustments in the operation of the FX. It is particularly useful

when multiple FX’s are connected together in the different stacking configurations to maximize the performance of the FX’s.

In most cases, the user will not need to adjust these settings from the factory default values.

ADV/FX/PAGE1--------
choose category:

ADV

INV

CHGR

PG2

ADV/FX/PAGE2--------
choose category:

PG1

GRID

GEN

PG3

ADV/FX/PAGE3--------
choose category:

PG2

AUX

STACK

PG4

ADV/FX/PAGE4--------
choose category:

PG3

SELL

CAL

MAIN

ADV/FX/CALIBRATE-P00
vac input

120 vac

adjustment
DOWN

INC

DEC

PORT

ADV/FX/CALIBRATE-P00
vac output

120 vac

adjustment
DOWN

INC

DEC

PORT

ADV/FX/CALIBRATE-P00
battery vdc 12.8 vdc
adjustment
DOWN

INC

DEC

PORT

ADV/FX/CALIBRATION--

calibration setup

completed

TOP

ADV

MAIN


Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is
displayed. Selecting shows a second screen of categories.

Selecting shows a third screen of categories.

Selecting shows a fourth screen of categories.


Selecting allows calibration of the AC input, AC output, and battery voltage set points.

The VAC INPUT ADJUSTMENT allows calibration of the AC input voltage. If the AC source is
measured and is different than the value read from the MATE, the user can adjust it to match the
measured value. This value can be raised by pressing the INC button. Conversely, this value can
be lowered by pressing the DEC button. The value can be raised or lowered up to 2 vac.

The VAC OUTPUT ADJUSTMENT allows calibration of the AC output voltage. If the AC output is
measured and is different than the value read from the MATE, the user can adjust the reading to
match the measured value. This value can be raised up to 2 vac by pressing the INC button and
lowered up to 2 vac by pressing the DEC button. NOTE: This only affects the MATE's voltage
display - See page 51 [ADJ. OUTPUT VOLTAGE] for actual adjustment of inverter VAC output.

The BATTERY VDC ADJUSTMENT allows calibration of the battery voltage. If the battery voltage
is measured and is different than the value read from the MATE, the user can adjust it to match the
measured value. This value can be raised by pressing the INC button. Conversely, this value can
be lowered by pressing the DEC button. The value can be raised or lowered up to 0.2 vdc for 12V
battery system, 0.4V for 24V battery systems, and 0.8V for 48Vbattery systems.

Selecting TOP returns the user to the top of the ADV/FX/CALIBRATION menu section. Selecting
ADV returns you to the advanced screen to allow selection of another product connected to the
MATE. Selecting MAIN returns the display to the MAIN screen.