MATE SCREENS

ERROR MENU

The ERROR section allows the user to check the cause of an error condition. When an error has occurred, the red error LED indicator

in the FX’s wiring compartment will be illuminated (not to be confused with a blinking “ERROR” LED that indicates a WARNING). If an

error occurs, the FX will cease operation and the MATE will display an error screen. Pressing from this screen brings

the user to the 1

st

screen of a list of error causes that will be available by pressing the DOWN button. The presence of the word “YES”

to the right of the appropriate cause indicates that this error has occurred. It is possible for multiple errors to occur simultaneously.

Check every error condition to make sure. An error can be cleared by pressing the button on the MATE and then turning the FX

and then . The inverter automatically resets from over-temperature and low or high battery voltage conditions.

MAIN----------------

6:54:42P

SUM STATUS SETUP ADV

STATUS--------------
choose product:

FX

MX

STATUS/FX/PAGE1-----
choose category:

MODES METER BATT PG2

STATUS/FX/PAGE2-----
choose category:

PG1 ERROR

WARN

PG3

STATUS/FX/ERROR—-P00
low ac output

No

voltage
DOWN

STATUS PORT

STATUS/FX/ERROR—-P00
stacking

No

error detected
DOWN

UP

TOP

PORT

STATUS/FX/ERROR—-P00
inverter

No

overtemp
DOWN

UP

TOP

PORT

STATUS/FX/ERROR—-P00
low battery

No

voltage
DOWN

UP

TOP

PORT

STATUS/FX/ERROR—-P00
phase loss

No

error
DOWN

UP

TOP

PORT

STATUS/FX/ERROR—-P00
high battery

No

voltage
DOWN

UP

TOP

PORT

STATUS/FX/ERROR—-P00
ac output

No

shorted
DOWN

UP

TOP

PORT

STATUS/FX/ERROR—-P00
ac output

No

backfeed
DOWN

UP

TOP

PORT

STATUS/FX/ERROR—-P00
end of error menu

UP

TOP STATUS

The MAIN screen is where the menu system starts. The four words in the bottom line of the
display correspond to the four buttons located below the display. The word in BOLD on the bottom
line indicates the selection used to advance the display to the next screen. Pressing the left two
buttons simultaneously from anywhere in the menu will return you to this screen.

Allows selection of the product type:

FX inverter/charger system

MX

MX60 PV MPPT charge controller

MODES

Status and allows adjustment of Inverter, AC input, Charger, Aux, and EQ

METER

Provides the AC voltages and currents of the FX

BATT

Provides the battery voltage and charger set points and timers

Displays additional sections – ERRORS, WARNINGS and PG3

PG1

Returns to page 1 of the STATUS section

Displays the different causes for errors and qualifies each cause with a Yes or No

WARN

Displays the different causes for warnings and qualifies each with a Yes or No

PG3

Displays additional sections – reason for last DISCONNECT and SELL

LOW AC OUTPUT VOLTAGE

indicates that the inverter was not able to maintain adequate AC

output voltage (105 VAC or above) to power the loads connected. This is typically caused by the
load demanding more power than the inverter is able to deliver.

STACKING ERROR DETECTED

indicates that a problem has occurred with the communication

cabling between stacked FX’s, or if the FX’s are stacked incorrectly. Check the stacking
programming. If this condition persists contact your dealer for servicing instructions.

INVERTER OVERTEMP

indicates that the FX reached its maximum allowed operating temp. This

can be caused by powering large AC loads or charging for too long. It can also be caused by
restricting the amount of air which is able to flow around the casting or operation in high temp
environments. The FX will automatically reset and resume operation once it cools down.

LOW BATTERY VOLTAGE

indicates that the battery voltage dropped below the LOW BATTERY

CUT-OUT VOLTAGE set point (default of 10.5 volts for a 12 volt FX) for 5 minutes. The inverter
will restart once the battery voltage exceeds the LOW BATTERY CUT-IN VOLTAGE set point
(default of 12.5 volts for a 12 volt FX) for 10 minutes.

PHASE LOSS ERROR

is not operational at this time. If a ‘Yes’ accompanies this Error, please

disregard and look for other error causes.

HIGH BATTERY VOLTAGE

indicates that the battery voltage rose above the high battery voltage

level (default of 20 volts for a 12 volt FX) for 10 seconds. The inverter will restart once the battery
voltage drops below the high battery voltage (default of 20 volts for a 12 volt FX) for 1 second.


AC OUTPUT SHORTED

indicates that the inverter immediately reached its maximum current and

shut down. This is usually caused by a short circuit condition (hence the AC OUTPUT SHORTED
label) but can also be caused by attempting to operate a load which far exceeds the inverter
output capability.

AC OUTPUT BACKFEED

indicates that another AC source of power was connected to the AC

output of the FX. Usually this is an installation issue. It often occurs when there is an X-240
transformer in the system that hasn’t been installed properly. Also, check that there are no
connections between the AC input and AC output circuitry.

Selecting TOP returns the user to the top of the STATUS/FX/ERROR menu section. Selecting
STATUS returns to the first page of the STATUS screen.