MATE SCREENS
ERROR MENU
The ERROR section allows the user to check the cause of an error condition. When an error has occurred, the red error LED indicator
in the FX’s wiring compartment will be illuminated (not to be confused with a blinking “ERROR” LED that indicates a WARNING). If an
error occurs, the FX will cease operation and the MATE will display an error screen. Pressing
the user to the 1
st
screen of a list of error causes that will be available by pressing the DOWN button. The presence of the word “YES”
to the right of the appropriate cause indicates that this error has occurred. It is possible for multiple errors to occur simultaneously.
Check every error condition to make sure. An error can be cleared by pressing the
and then
MAIN----------------
6:54:42P
SUM STATUS SETUP ADV
↓
STATUS--------------
choose product:
FX
MX
↓
STATUS/FX/PAGE1-----
choose category:
MODES METER BATT PG2
↓
STATUS/FX/PAGE2-----
choose category:
PG1 ERROR
WARN
PG3
↓
STATUS/FX/ERROR—-P00
low ac output
No
voltage
DOWN
STATUS PORT
↓
STATUS/FX/ERROR—-P00
stacking
No
error detected
DOWN
UP
TOP
PORT
↓
STATUS/FX/ERROR—-P00
inverter
No
overtemp
DOWN
UP
TOP
PORT
↓
STATUS/FX/ERROR—-P00
low battery
No
voltage
DOWN
UP
TOP
PORT
↓
STATUS/FX/ERROR—-P00
phase loss
No
error
DOWN
UP
TOP
PORT
↓
STATUS/FX/ERROR—-P00
high battery
No
voltage
DOWN
UP
TOP
PORT
↓
STATUS/FX/ERROR—-P00
ac output
No
shorted
DOWN
UP
TOP
PORT
↓
STATUS/FX/ERROR—-P00
ac output
No
backfeed
DOWN
UP
TOP
PORT
↓
STATUS/FX/ERROR—-P00
end of error menu
UP
TOP STATUS
The MAIN screen is where the menu system starts. The four words in the bottom line of the
display correspond to the four buttons located below the display. The word in BOLD on the bottom
line indicates the selection used to advance the display to the next screen. Pressing the left two
buttons simultaneously from anywhere in the menu will return you to this screen.
Allows selection of the product type:
FX inverter/charger system
MX
MX60 PV MPPT charge controller
MODES
Status and allows adjustment of Inverter, AC input, Charger, Aux, and EQ
METER
Provides the AC voltages and currents of the FX
BATT
Provides the battery voltage and charger set points and timers
Displays additional sections – ERRORS, WARNINGS and PG3
PG1
Returns to page 1 of the STATUS section
Displays the different causes for errors and qualifies each cause with a Yes or No
WARN
Displays the different causes for warnings and qualifies each with a Yes or No
PG3
Displays additional sections – reason for last DISCONNECT and SELL
LOW AC OUTPUT VOLTAGE
indicates that the inverter was not able to maintain adequate AC
output voltage (105 VAC or above) to power the loads connected. This is typically caused by the
load demanding more power than the inverter is able to deliver.
STACKING ERROR DETECTED
indicates that a problem has occurred with the communication
cabling between stacked FX’s, or if the FX’s are stacked incorrectly. Check the stacking
programming. If this condition persists contact your dealer for servicing instructions.
INVERTER OVERTEMP
indicates that the FX reached its maximum allowed operating temp. This
can be caused by powering large AC loads or charging for too long. It can also be caused by
restricting the amount of air which is able to flow around the casting or operation in high temp
environments. The FX will automatically reset and resume operation once it cools down.
LOW BATTERY VOLTAGE
indicates that the battery voltage dropped below the LOW BATTERY
CUT-OUT VOLTAGE set point (default of 10.5 volts for a 12 volt FX) for 5 minutes. The inverter
will restart once the battery voltage exceeds the LOW BATTERY CUT-IN VOLTAGE set point
(default of 12.5 volts for a 12 volt FX) for 10 minutes.
PHASE LOSS ERROR
is not operational at this time. If a ‘Yes’ accompanies this Error, please
disregard and look for other error causes.
HIGH BATTERY VOLTAGE
indicates that the battery voltage rose above the high battery voltage
level (default of 20 volts for a 12 volt FX) for 10 seconds. The inverter will restart once the battery
voltage drops below the high battery voltage (default of 20 volts for a 12 volt FX) for 1 second.
AC OUTPUT SHORTED
indicates that the inverter immediately reached its maximum current and
shut down. This is usually caused by a short circuit condition (hence the AC OUTPUT SHORTED
label) but can also be caused by attempting to operate a load which far exceeds the inverter
output capability.
AC OUTPUT BACKFEED
indicates that another AC source of power was connected to the AC
output of the FX. Usually this is an installation issue. It often occurs when there is an X-240
transformer in the system that hasn’t been installed properly. Also, check that there are no
connections between the AC input and AC output circuitry.
Selecting TOP returns the user to the top of the STATUS/FX/ERROR menu section. Selecting
STATUS returns to the first page of the STATUS screen.