Mate screens, Page 55, Grid menu – Outback Power Systems FX 2012T User Manual
Page 55
Copyright 2003
OutBack Power Systems, Inc.
FX & VFX Series Inverter/Charger System Installation & Programming Manual
19009 62
nd
Ave NE, Arlington WA 98223 USA
900-0027-1
Tel 360 435 6030 Fax 360 435 6019
Rev 7.2
08/26/05
Page 55
MATE SCREENS
GRID MENU
The GRID category of the advanced menu section allows for adjustment of the AC input voltage window and time delays to match the
characteristics of the AC source if that AC source is the utility grid. This setting can be found in the SETUP/FX/INPUT menu. Only
“Grid-Tie” FX’s have a default of GRID as the AC source. All other FX types have an AC input default of GEN. If the users AC source
is the utility grid, return to the SETUP/FX/INPUT section (page 49) and change the ‘AC Transfer Control’ screen to GRID.
ADV-----------------
choose product:
FX
MATE
↓
ADV/FX/PAGE1--------
choose category:
ADV
INV
CHGR
PG2
↓
ADV/FX/PAGE2--------
choose category:
PG1
GRID
GEN
PG3
↓
ADV/FX/GRID------P00
ac input
00.5 min
connect delay
DOWN
INC
DEC
PORT
↓
ADV/FX/GRID------P00
ac1/grid
108 vac
lower limit
DOWN
INC
DEC
PORT
↓
ADV/FX/GRID------P00
ac1/grid
140 vac
upper limit
DOWN
INC
DEC
PORT
↓
ADV/FX/GRID------P00
ac1/grid
60.0 aac
input limit
DOWN
INC
DEC
PORT
↓
ADV/FX/GRID------P00
ac1/grid
6 cycles
transfer delay
DOWN
INC
DEC
PORT
↓
ADV/FX/GRID---------
GRID programming
completed
TOP
ADV
MAIN
Once the password has been correctly entered, the ADV - CHOOSE PRODUCT is displayed.
Selecting
Selecting
Selecting
The AC INPUT CONNECT DELAY set point adjusts the time period of when the FX sees an
acceptable AC source to when it connects the AC loads to that source. This is useful to allow the
utility grid to become stable after a utility power outage. This setting has a range between 0.2
minutes to 15 minutes in 0.1 minute increments.
The AC1/GRID LOWER LIMIT set point allows adjustment of the minimum voltage that the AC
source is allowed to be in order for the FX to connect to that source. The FX will back off the
charger if the AC source is at this lower limit. If the AC source falls below this limit, the FX will
disconnect from the AC source until it is above this value. This setting has a range between 70
vac and 110 vac in 1 vac increments.
The AC1/GRID UPPER LIMIT set point allows adjustment of the maximum voltage that the AC
source is allowed to be in order for the FX to connect to that source. If the AC source exceeds
this value, the FX will disconnect from the AC source until it is below this value. This setting has a
range between 130 vac and 150 vac in 1 vac increments.
The AC1/GRID INPUT LIMIT sets the maximum amount of current the FX allows to be drawn
from the AC source. When the AC input current limit is reached, the power draw of the battery
charger is backed off to prevent overloading the AC source. If the AC loads exceed this limit, the
FX will give a warning and start blinking the red “ERROR” LED. This setting has a range between
5.0 aac and 60.0 aac in 1.0 aac increments.
The AC1/GRID TRANSFER DELAY is the amount of time that the AC input will remain connected
to the AC source when the AC input voltage drops below the AC1/GRID lower limit setting. Once
the AC voltage has risen above the AC1/GRID lower limit setting for the AC INPUT CONNECT
DELAY time period, the AC source will be reconnected. This setting has a range between 0
cycles and 240 cycles in 1 cycle increments.
Selecting TOP returns the user to the top of the ADV/FX/GRID menu section. Selecting ADV
returns you to the advanced screen to allow selection of another product connected to the MATE.
Selecting MAIN returns the display to the MAIN screen.