MATE SCREENS
DISCONNECT MENU
The FX includes a section that displays the reason for last DISCONNECT from the AC source. This is helpful if the FX rejects the AC
source and the user wants an explanation and help on rectifying the problem. The FX will disconnect from an AC source if the AC
source falls out of the FX’s frequency or voltage ranges. If the AC source disconnects from the FX and none of the reasons for
disconnect are followed by a “Yes” it is possible that the AC source shut itself down (this is sometimes the case with smaller generators,
or generators with an internal temperature “shutdown” switch).
MAIN----------------
6:54:42P
SUM STATUS SETUP ADV
↓
STATUS--------------
choose product:
FX
MX
↓
STATUS/FX/PAGE1-----
choose category:
MODES METER BATT PG2
↓
STATUS/FX/PAGE2-----
choose category:
PG1 ERROR
WARN
PG3
↓
STATUS/FX/PAGE3-----
choose category:
PG2 DISCON SELL MAIN
↓
STATUS/FX/DISCON-P00
acin freq
No
too high
DOWN
STATUS PORT
↓
STATUS/FX/DISCON-P00
acin freq
No
too low
DOWN
UP
TOP
PORT
↓
STATUS/FX/DISCON-P00
acin voltage
No
> max
DOWN
UP
TOP
PORT
↓
STATUS/FX/DISCON-P00
acin voltage
No
< min
DOWN
UP
TOP
PORT
↓
STATUS/FX/DISCON----
end of DISCON menu
UP
TOP STATUS
The MAIN screen is where the menu system starts. The four words in the bottom line of the display
correspond to the four buttons located below the display. The word in BOLD on the bottom line
indicates the selection used to advance the display to the next screen. Pressing the left two buttons
simultaneously from anywhere in the menu will return you to this screen.
Allows selection of the product type:
FX inverter/charger system
MX
MX60 PV MPPT charge controller
MODES
Status and allows adjustment of Inverter, AC input, Charger, Aux, and EQ
METER
Provides the AC voltages and currents of the FX
BATT
Provides the battery voltage and charger set points and timers
Displays additional sections – ERRORS, WARNINGS and PG3
PG1
Returns to page 1 of the STATUS section
ERROR
Displays the different causes for errors and qualifies each cause with a Yes or No
WARN
Displays the different causes for warnings and qualifies each with a Yes or No
Displays additional sections – reason for last DISCONNECT and SELL
PG2
Displays additional sections – ERRORS, WARNINGS and PG3
Displays the reason that the FX last disconnected from the AC source
SELL
Displays the code related to the reason for the last disconnection while selling
MAIN
Returns the user to the MAIN menu
The ACIN FREQ TOO HIGH screen displays a “Yes” if the FX disconnected from the AC source due
to the frequency of the AC source exceeding 69 Hz. The MATE does not display the frequency of
the AC source, but this can be verified using an oscilloscope. If this message occurs and the AC
source is a generator, it may be possible to adjust the frequency of the generator.
The ACIN FREQ TOO LOW screen displays a “Yes” if the FX disconnected from the AC source due
to the frequency of the AC source being below 51 Hz. The MATE does not display the frequency of
the AC source, but this can be verified using an oscilloscope. If this message occurs and the AC
source is a generator, it may be possible to adjust the frequency of the generator.
The ACIN VOLTAGE > MAX screen indicates that the AC source’s voltage exceeded the maximum
AC voltage the FX allows (140 vac default). This value can be adjusted in the ADVANCED menu, in
the GRID or GEN sections (depending on your input type). The FX disconnects to protect the loads
from high voltage. If you expect significant voltage drop due to long cable runs, it may be safe to
raise the limit. This screen is not operational at this time.
The ACIN VOLTAGE < MIN screen indicates that the AC source’s voltage is below the minimum AC
voltage the FX allows (108 vac default). This value can be adjusted in the ADVANCED menu, in the
GRID or GEN sections (depending on your input type). The FX disconnects to protect the loads from
low voltage. If your AC source operates near this voltage limit, it could affect the charging function
(the FX backs off the charger if the AC voltage reaches the lower limit) and adjusting the limit lower
may be in order. This screen is not operational at this time.
Selecting TOP returns the user to the top of the STATUS/FX/DISCON menu section. Selecting
STATUS returns to the STATUS screen to allow selection of another product.