beautypg.com

Mate screens, Page 48, Disconnect menu – Outback Power Systems FX 2012T User Manual

Page 48

background image

Installation & Programming Manual

FX & VFX Series Inverter/Charger System

Copyright 2003

OutBack Power Systems, Inc.

900-0027-1

19009 62

nd

Ave NE, Arlington WA 98223 USA

Page 48

Rev 7.2

08/26/05 Tel 360 435 6030 Fax 360 435 6019

MATE SCREENS

DISCONNECT MENU

The FX includes a section that displays the reason for last DISCONNECT from the AC source. This is helpful if the FX rejects the AC
source and the user wants an explanation and help on rectifying the problem. The FX will disconnect from an AC source if the AC
source falls out of the FX’s frequency or voltage ranges. If the AC source disconnects from the FX and none of the reasons for
disconnect are followed by a “Yes” it is possible that the AC source shut itself down (this is sometimes the case with smaller generators,
or generators with an internal temperature “shutdown” switch).

MAIN----------------

6:54:42P

SUM STATUS SETUP ADV

STATUS--------------
choose product:

FX

MX

STATUS/FX/PAGE1-----
choose category:

MODES METER BATT PG2

STATUS/FX/PAGE2-----
choose category:

PG1 ERROR

WARN

PG3

STATUS/FX/PAGE3-----
choose category:

PG2 DISCON SELL MAIN

STATUS/FX/DISCON-P00
acin freq

No

too high
DOWN

STATUS PORT

STATUS/FX/DISCON-P00
acin freq

No

too low
DOWN

UP

TOP

PORT

STATUS/FX/DISCON-P00
acin voltage

No

> max
DOWN

UP

TOP

PORT

STATUS/FX/DISCON-P00
acin voltage

No

< min
DOWN

UP

TOP

PORT

STATUS/FX/DISCON----
end of DISCON menu

UP

TOP STATUS

The MAIN screen is where the menu system starts. The four words in the bottom line of the display
correspond to the four buttons located below the display. The word in BOLD on the bottom line
indicates the selection used to advance the display to the next screen. Pressing the left two buttons
simultaneously from anywhere in the menu will return you to this screen.

Allows selection of the product type:

FX inverter/charger system

MX

MX60 PV MPPT charge controller

MODES

Status and allows adjustment of Inverter, AC input, Charger, Aux, and EQ

METER

Provides the AC voltages and currents of the FX

BATT

Provides the battery voltage and charger set points and timers

Displays additional sections – ERRORS, WARNINGS and PG3

PG1

Returns to page 1 of the STATUS section

ERROR

Displays the different causes for errors and qualifies each cause with a Yes or No

WARN

Displays the different causes for warnings and qualifies each with a Yes or No

Displays additional sections – reason for last DISCONNECT and SELL

PG2

Displays additional sections – ERRORS, WARNINGS and PG3

Displays the reason that the FX last disconnected from the AC source

SELL

Displays the code related to the reason for the last disconnection while selling

MAIN

Returns the user to the MAIN menu

The ACIN FREQ TOO HIGH screen displays a “Yes” if the FX disconnected from the AC source due
to the frequency of the AC source exceeding 69 Hz. The MATE does not display the frequency of
the AC source, but this can be verified using an oscilloscope. If this message occurs and the AC
source is a generator, it may be possible to adjust the frequency of the generator.

The ACIN FREQ TOO LOW screen displays a “Yes” if the FX disconnected from the AC source due
to the frequency of the AC source being below 51 Hz. The MATE does not display the frequency of
the AC source, but this can be verified using an oscilloscope. If this message occurs and the AC
source is a generator, it may be possible to adjust the frequency of the generator.

The ACIN VOLTAGE > MAX screen indicates that the AC source’s voltage exceeded the maximum
AC voltage the FX allows (140 vac default). This value can be adjusted in the ADVANCED menu, in
the GRID or GEN sections (depending on your input type). The FX disconnects to protect the loads
from high voltage. If you expect significant voltage drop due to long cable runs, it may be safe to
raise the limit. This screen is not operational at this time.
The ACIN VOLTAGE < MIN screen indicates that the AC source’s voltage is below the minimum AC
voltage the FX allows (108 vac default). This value can be adjusted in the ADVANCED menu, in the
GRID or GEN sections (depending on your input type). The FX disconnects to protect the loads from
low voltage. If your AC source operates near this voltage limit, it could affect the charging function
(the FX backs off the charger if the AC voltage reaches the lower limit) and adjusting the limit lower
may be in order. This screen is not operational at this time.

Selecting TOP returns the user to the top of the STATUS/FX/DISCON menu section. Selecting
STATUS returns to the STATUS screen to allow selection of another product.

This manual is related to the following products: