Series/parallel quad fx system, Page 20 – Outback Power Systems FX 2012T User Manual
Page 20
Installation & Programming Manual
FX & VFX Series Inverter/Charger System
Copyright 2003
OutBack Power Systems, Inc.
900-0027-1
19009 62
nd
Ave NE, Arlington WA 98223 USA
Page 20
Rev 7.2
08/26/05 Tel 360 435 6030 Fax 360 435 6019
FX SYSTEM CONFIGURATION – SERIES/PARALLEL QUAD FX SYSTEM
Series/Parallel Quad FX System
The following diagram illustrates a typical series/parallel FX installation using four FX’s. This diagram is for a non-Mobile FX
installation only. Below this diagram are notes for how to change this diagram to accommodate a Mobile installation. The AC
wiring from the AC source and to the AC loads must handle 120 amps AC or more. The AC wiring connected to the QUO 100A dual
bypass breakers must handle 100 amps AC or more. All other AC wiring must handle a capacity of 50 amps AC or more. For a
‘Mobile’ FX system, 30A input breakers should be used due to the maximum AC input pass-through rating of the Mobile FX’s. This type
of FX system can continuously power 8-14.4KW of loads depending on which model is used. Connecting more power than the
continuous rating of the FX may cause breakers to trip or the FX to shut off its AC output. A HUB, MATE and X-240 must be connected
to successfully stack these FX’s in series/parallel. The MATE must be connected to adjust any parameters or to display any meters.
Once the FX’s have been programmed using the MATE, the MATE can be disconnected. The programming will be saved within the
FX’s non-volatile memory even if the FX is completely shut down.
NOTES:
Program the top FX as the Master (1-2PH MASTER), the first Slave as an Outback L1 slave (OB Slave L1), and the second
and third Slaves as OutBack L2 slaves (OB SLAVE L2). See the STACKING INFORMATION section of the manual for more info.
In systems that include three or more FX’s and must be series stacked, an X-240 autotransformer must be used. When the FX’s are
connected in series for 120/240 VAC, the X-240 can be connected to the two AC output legs to allow all of the FX’s capacity to be
available on either of the 120 VAC output circuits. This allows higher efficiency and better performance as heavy 120 VAC loads are
powered by more of the FX’s. The X-240 also allows the master to power loads on either of the 120 VAC output circuits with the slave
off. This reduces the idle power consumption and improves the system efficiency.
NON-MOBILE FX NOTES:
The AC OUTPUT NEUTRAL IS NOT BONDED TO THE CHASSIS OR THE GROUND TERMINAL of
the FX system. This connection is to be made by the installer either in the AC service entrance or within the AC load distribution panel
of the electrical system. The AC input, AC output and DC terminals are isolated from the metal chassis of the FX. Proper grounding of
these circuits and the chassis of the FX is the responsibility of the installer.
MOBILE FX NOTES:
The AC input source to the FX (grid and/or generator) must have an internal neutral-ground connection. On
the above diagram the AC source’s neutral conductor must go directly to the FXs AC NEUTRAL IN terminal or to a separate neutral
busbar that is isolated from the FX’s AC output neutral. The AC output of the FX must go to a separate AC output busbar that is
isolated from the AC input neutral. A bypass mechanism must bypass the AC source’s hot and neutral wires. Proper grounding of the
DC circuit and the chassis of the FX is the responsibility of the installer.