beautypg.com

Mate screens, Page 60, Sell menu – Outback Power Systems FX 2012T User Manual

Page 60

background image

Installation & Programming Manual

FX & VFX Series Inverter/Charger System

Copyright 2003

OutBack Power Systems, Inc.

900-0027-1

19009 62

nd

Ave NE, Arlington WA 98223 USA

Page 60

Rev 7.2

08/26/05 Tel 360 435 6030 Fax 360 435 6019

MATE SCREENS

SELL MENU

The SELL menu is used to set the functions that control the process of selling power back to the utility grid. This menu only pertains to
Grid-Tied FX’s. These functions include setting the voltage at which the FX sells back to the utility grid, setting the window in which the
Grid-Tie function operates, and to enable or disable the Grid-Tie function. The default values enable the FX to sell back to the utility
grid after the FX has completed a charge cycle. To disable this charge cycle, press the “hot” button four times, press

, press and then press . The FX waits 5 minutes after it has accepted the utility grid as an AC source and must

be above the “sell RE volts” (found in this menu) to start selling.

ADV/FX/PAGE1--------
choose category:

ADV

INV

CHGR

PG2

ADV/FX/PAGE2--------
choose category:

PG1

GRID

GEN

PG3

ADV/FX/PAGE3--------
choose category:

PG2

AUX

STACK

PG4

ADV/FX/PAGE4--------
choose category:

PG3

SELL

CAL

MAIN

ADV/FX/SELL------P00
sell re

12.8vdc

volts
DOWN

INC

DEC

PORT

ADV/FX/SELL------P00
grid tie

IEEE

window
DOWN

IEEE USER PORT

ADV/FX/SELL------P00
grid tie

GridTie

authority
DOWN

INC

DEC

PORT

ADV/FX/SELL------

selling setup

completed

TOP

ADV

MAIN

Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is
displayed. Selecting shows a second screen of categories.

Selecting shows a third screen of categories.

Selecting shows a fourth screen of categories.


Selecting allows adjustment of the Grid-tie and selling set points and operation.



The SELL RE VOLTS (RE = Renewable Energy) screen allows the user to set the voltage at
which they would like to sell battery power back to the utility grid. If the battery voltage is above
the voltage shown on this screen and the FX isn’t charging then the FX will sell power back to
the utility grid. This setting has a range between 10.0 vdc and 15.0 vdc in 0.1vdc increments.

The GRID TIE WINDOW screen controls the voltage and frequency windows that the grid-tie
function operates in. If the FX repeatedly disconnects from the utility grid this value may need to
be changed. This function should not, I repeat, should not be changed without consulting
OutBack Power Systems first.

The GRID TIE AUTHORITY screen allows the user to turn on or off the selling function of the FX.
When the screen displays “GridTie” (default), the FX will sell power under the correct conditions.
Pressing DEC will change “GridTie” to “No Sell” and the selling function will be disabled.
Pressing INC will change the display back from “No Sell” to “GridTie”.

Selecting TOP returns the user to the top of the ADV/FX/SELL menu section. Selecting ADV
returns you to the advanced screen to allow selection of another product connected to the MATE.
Selecting MAIN returns the display to the MAIN screen.












This manual is related to the following products: