Explicit message send, Response codes, Command block response block response codes – Omron SYSMAC CJ1W-EIP21 User Manual
Page 442: Subnet mask (response)
![background image](/manuals/203516/442/background.png)
416
FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports
Appendix E
IP Address (Response)
The local IP address set in the CPU Bus Unit System Setup for the EtherNet/IP Unit or built-in EtherNet/IP port
is returned in order starting from the leftmost bytes in hexadecimal. If the local IP address set in the allocated
words in the DM Area is enabled, 0.0.0.0 is returned.
Subnet Mask (Response)
The subnet mask set in the CPU Bus Unit System Setup for the EtherNet/IP Unit or built-in EtherNet/IP port is
returned in order starting from the leftmost bytes in hexadecimal.
Response Codes
EXPLICIT MESSAGE SEND
Sends a explicit request message to the specified object, and receives a response.
The rightmost 8 bits of the remote (destination) IP address are used as the remote MAC ID, and the remote IP
address is the network ID of the local IP address + the rightmost 8 bits of the remote IP address.
Command Block
Response Block
Response Codes
Response code
Description
0000
Normal end
1001
Command too large
28
01
Command
code
Class ID
Instance ID
Service Data
Destination node address
Service Code
468 bytes max.
28
01
Command
code
End
code
Number of
bytes received
Service Data
Destination node address (remote node)
Service Code
498 bytes max.
00
00
Response code
Description
0000
Normal end
0101
The local node’s network has not started up.
0105
Local node setting error (A BOOTP errors occurs, and the IP
address is undetermined.)
0106
Duplicate address error
0201
The remote node’s network has not started up.
0204
Remote node busy, cannot send.
0205
No response returned from remote node. Monitoring timer
timed out.
1001
Command length exceeds maximum command length.
1002
Command length is less than minimum command length.
1004
Command block format does not match.
1005
Header error