Omron SYSMAC CJ1W-EIP21 User Manual
Page 272
![background image](/manuals/203516/272/background.png)
246
Sending Explicit Messages
Section 9-1
D01016 = 382E hex
IP address: “8.”
D01017 = 3235 hex
IP address: “25”
D01018 = 302E hex
IP address: “0.”
D01019 = 3200 hex
IP address: “2”
Padding data: 00 hex
D = D02000:
First response word at local node
C = D00000:
First control word
D00000 = 0028 hex
Number of command bytes: 40 bytes
D00001 = 0064 hex
Number of response bytes: 100 bytes
D00002 = 0001 hex
Destination network address: 1
D00003 = 0510 hex
Destination node address: 5
Destination unit address: FE hex (or 10 hex)
D00004 = 0000 hex
Response, communications port 0, no retries
D00005 = 00A0 hex
Response monitoring time: 16.0 s
Response
D02000 = 2801 hex
Command code
D02001 = 0000 hex
FINS completion code
D02002 = 0000 hex
Transport ID
D02003 = 001D hex
Number of bytes received: 29 bytes
D02004 = 8100 hex
Service code (response): 81 hex
Reserved: 00 hex
D02005 = 0000 hex
General status: 00 hex
Reserved: 00 hex
Words C+6 to C+18 contain the service response data.
D02006: 2F00 hex
D02007: 0C00 hex
D02008: 0C00 hex
D02009: 0101 hex
D020010: 3000 hex
D020011: 5303 hex
D020012: 0011 hex
D020013: 0A43 hex
D020014: 5331 hex
D020015: 572D hex
D020016: 4549 hex
D020017: 5032 hex
D020018: 3100 hex