CIO Area Allocations
Section 4-2
Communications
Status 1
(EtherNet/IP Unit to
CPU Unit) (n + 12)
Word n+12 contains status flags related to the tag data links, as shown in the
following diagram.
15
Error Log Stored
ON
Unit
Indicates that an error record
is registered in the error log.
OFF
Unit
Indicates that no error records
are registered in the error log.
Also turned OFF when an
error log clear request is
received.
Bit
Name
Status
Manipulated
by
Unit operation
Bit
Name
Status
Manipulated
by
Unit operation
0
Verification Error
ON
Unit
Indicates that the information
registered for a target node in
the tag data link parameters is
different from the actual node
information.
Main causes:
• The specified target does not
exist.
• The variable name does not
match.
• The connection size is differ-
ent.
• Connection resources are
insufficient.
OFF
Unit
Indicates that a verification
error has not occurred. Also
turned OFF when a verifica-
tion error is cleared.
1
(Not used)
---
---
---
2
Tag Data Link Error ON
Unit
Indicates that there were two
or more errors in a connection
as an originator.
This status does not indicate
the following errors.
• Connection as a target
• Connection timeout due to a
Link OFF Error with the
switching hub
OFF
Unit
Indicates that the errors listed
above did not occur.
3
(Not used)
---
---
---
n+12
Tag Data Link Error
Invalid Communications Parameter
All Tag Data Links Operating
Verification Error
Tag Refresh Error
Tag Data Links Operating
Tag Database Error
15 14
13
12
11
10
9
8
7
6
5
4
3
2
1
0