Omron SYSMAC CJ1W-EIP21 User Manual
Page 102
![background image](/manuals/203516/102/background.png)
76
CIO Area Allocations
Section 4-2
1
Tag Data Link
Operating
ON
Unit
Indicates that the tag data link
is operating. Turned OFF
when communications stop in
the following cases.
• Hardware error
• IP Address Duplication Error
• BOOTP Server Error
• Basic Ethernet Settings
Error
• Memory Error (MAC
Address Error)
OFF
Unit
Indicates that the tag data link
is stopped. Turned ON in the
following cases.
• The Unit is set as the origi-
nator and the power supply
was turned ON or the Unit
was restarted.
• The Unit is set as the origi-
nator and the Tag Data Link
Start Bit was turned ON.
2
Operating IP
Address Change
ON
Unit
ON if the node address set-
ting is different from the set-
ting when the power was
turned ON.
OFF
Unit
OFF if the node address set-
ting is the same as the setting
when the power was turned
ON.
3 to 10
(Not used)
---
---
---
11
User Setting Area
Enabled
ON
Unit
Indicates that the user set-
tings area data is enabled.
ON when “user settings” have
been specified as the layout of
the allocated CIO Area, and
refreshing of the user settings
area has started.
OFF
Unit
Indicates that the user set-
tings area data is invalid.
The bit is turned OFF in the
following cases, because
communications stop.
• The allocated CIO Area lay-
out is set to default settings.
• The allocated CIO Area lay-
out is set to user settings,
but one of the following prob-
lems occurred.
• A Layout Setting Error
occurred.
12 to
13
(Not used)
---
---
---
14
Multiple Switches
ON Error
ON
Unit
ON when two or more control
bits are ON simultaneously.
(Unused bits are ignored.)
OFF
Unit
Turned OFF when the next
control bit operation starts.
Bit
Name
Status
Manipulated
by
Unit operation