Controller status read, Response codes, Command block response block parameters – Omron SYSMAC CJ1W-EIP21 User Manual
Page 420: Communications status 3 (response)
![background image](/manuals/203516/420/background.png)
394
FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports
Appendix E
Response Codes
CONTROLLER STATUS READ
Reads the controller status.
Command Block
Response Block
Parameters
Communications Status 3 (Response)
Ethernet Basic Setting Error
IP Address Table Error
Response code
Description
0000
Normal end
1001
Command too large
06 01
Command code
06 01
4 byte
4 byte
Total number
of
packets sent
4 byte
Total number
of
send errors
4 byte
Total number
of
send collisions
4 byte
Response
code
Command
code
2 byte
Total number
of
packets received
Total number
of
receive errors
Communications
status 3
Bit 3: IP address table error
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Bit 4: IP router table error
Bit 6: Routing table error
Bit 15: Non-volatile memory error
Bit 14: Address mismatch
Bit 2: EtherNet/IP basic setting error
Bit 9: EtherNet/IP advanced setting error
Bit 10: BOOTP server error
Bit 11: SNTP server error
Bit 2
Meaning
0
No error
1
An error (such as an invalid IP address) was detected during the validity check of parameters related to the
TCP/IP Interface Object and Ether Link Object.
Bit 3
Meaning
0
No error
1
Error detected (More than 32 records, invalid IP address, or invalid FINS node address).