3-13
The External Counter output, available at the two
terminals labeled CTR on the Main PCB, is influenced by
the TOTAL MULT value. Since the output is designed to
operate electromechanical accumulators, large flow rates
will require that the TOTAL MULT be set to a value usable
by these types of counters (typically speeds no faster than
3 cps). The following chart tabulates suggested settings
vs. flow ranges:
TOTAL ON/OFF
This key has three functions:
Exponent
Multiplier
Useable CTR
Range:
GPM or LPM
0
X1
30-600
1
X10
300-6,000
2
X100
3,000-60,000
3
X1,000
30,000-600,000
4
X10,000
300,000-6,000,000
Key press number
Operation
First press
Stops the internal totalizer/
external CTR and displays
the last value
Second press
Resets the internal totalizer
to zero
(continued)
PART 3 - KEYPAD CONFIGURATION