3-5
The 4-20mA output is proportional to the flow rate 
measuring scale and can drive a load of up to 1000 ohms. 
The output is isolated from earth ground and circuit low. 
Connect the load to the 4-20 mA connection terminals 
located on the inside of the enclosure, matching polarity
as indicated.
Line power is connected by supplying power to the 
appropriate terminals located inside of the enclosure 
Use wiring practices that conform to local codes
(National Electric Code Hand book in the USA). 
Use only the standard three wire connection. The ground 
terminal grounds the instrument, which is mandatory for 
safe operation. 
CAUTION:  Any other wiring method may be unsafe or 
cause improper operation of the instrument. 
It is recommended not to run line power with other signal 
wires within the same wiring tray or conduit. Verify that 
the power supply jumper connections are oriented cor-
rectly for the power source being wired. The electronics 
can be damaged if improper power is connected or if 
jumpers are not installed correctly. The DC input is not 
fuse protected. It is recommended that an external fuse 
be installed if DC power is selected. The fuse should be a 
1A delay action type. See Figure 3.4 
 Power Source Jumpers
 115 VAC JP8, JP10, JP11 
 230 VAC JP9, JP11 
 100 VAC JP7 
 12 VDC JP3, JP5 
 24 VDC JP4, JP6 
NOTE: This instrument requires clean electrical line 
power. Do not connect the meter on a circuit which oper-
ates lighting ballasts, motors, solenoids, etc. 
PART 2 - SERVICE AND MAINTENANCE
PART 3 - TRANSMITTER INSTALLATION
4-20mA OUTPUT
Power Connections
Figure 3.4
Power Supply Jumper
Selection