Omega FD6003 User Manual
Page 19

3-3
1. Place the transmitter in a location that is:
♦
Where little vibration exist.
♦
Protected from falling corrosive fluids.
♦
Within ambient temperature limits - 22 to 122°F [-30 to 
50°C] 
♦
Out of direct sunlight. Direct sunlight may increase 
temperatures within the transmitter to above maximum 
limit. 
2. Mounting: Refer to Figure 3.3 for enclosure and
mounting dimension details. Ensure that enough room 
is available to allow for door swing, maintenance and 
conduit entrances. Secure the enclosure to a flat 
surface with four appropriate fasteners. 
3. Conduit holes. Conduit hubs should be used where
cables enter the enclosure. Holes not used for cable 
entry should be sealed with plugs. 
NOTE: Use NEMA 4 [ IP65 ] rated fittings and plugs to 
maintain the water tight integrity of the enclosure. 
Generally, the right conduit hole (viewed from front) is 
used for line power; the left conduit hole for transducer 
connections. 
4. If additional holes are required, (analog outputs, etc.)
drill the appropriate size hole in the enclosure’s 
bottom. Use extreme care not to run the drill bit into 
the wiring or circuits cards. 
To access terminal strips for electronic connectors, loosen 
the two screws in the enclosure door and open the door. 
PART 2 - ELECTRICAL CONNECTIONS
PART 3 - TRANSMITTER INSTALLATION
Transmitter 
Installation 