FPI P36-4 Zero Clearance Direct Vent Gas Fireplace

16

INSTALLATION

When installing the optional Tripoli Screen Door Series, a non-combustible material 12" (305mm) above the unit and 6" (153mm) on each side
must be used (see Diagram 2). For complete framing details see page 57.

The Tripoli Screen Door Series also requires steel stud framing above and on each side of the unit (refer to Diagram 2).

REGENCY

®

TRIPOLI SCREEN DOOR SERIES FRAMING NOTE

Diagram 2