LEAD LAG, NIGHT SET BACK

Automatic Lead Lag

*Lead Change Hours
Designated lead boiler will change when remaining hours reaches 0.
Range 0-225 hrs. Default value is 100 hrs.
If set at 0 hours lead will not change.
Hours remaining will automatically total.

Enter the desired number of hours of lead boiler operation before change. Hours re-
maining is automatically calculated. Designated lead boiler will change as soon as
remaining hours run out. Set at 0 hours and lead will not change.

STANDARD
BOILER PARAMETERS

LEAD LAG, NIGHT SET BACK

Boiler Parameters

*Pump delay selectable from 0 to 20

*Ignition time sets the duration to monitor

minutes. Range 0-20. Default value 3 mins.

Ignition prior to lock out. Range 15-100.
Default value 30 secs.

PUSH SELECT
PUMP DELAY
Enter time desired for boiler pump operation, if one is installed and wired to boiler moni-
tor. If there is no pump or a continuous running pump, ignore.

PUSH SELECT

IGN TIME
Display shows time of monitoring the ignition prior to main flame. Default timing is 30
seconds.
Note: On multiple boilers, a time must be entered for each boiler.