POWER TEST

CHECK POWER

Utilizing a Volt-Ohm-Meter (VOM) monitor the following on the "System Control Module"
and "Boiler Monitor(s)" for proper voltage levels.

POWER TEST TABLE

Module

Test Points

Indication

System Control

TB1-1- TB1-2

108 VAC to 132 VAC

System Control

TB1-1- TB1-3

108 VAC to 132 VAC

System Control

TB1-2- TB1-3

LESS THAN 1 VAC

System Control

TB1-1 - I

108 VAC to 132 VAC

System Control

TB1-2 - I

LESS THAN 1 VAC

System Control

TB1-3 - I

LESS THAN 0.5 VAC

Module

Test Points

Indication

Boiler Monitor

TB1-1- TB1-2

108 VAC to 132 VAC

Boiler Monitor

TB1-1- TB1-3

108 VAC to 132 VAC

Boiler Monitor

TB2-2- TB2-3

LESS THAN 1 VAC

Boiler Monitor

TB1 -1 - I

108 VAC to 132 VAC

Boiler Monitor

TB2 -2 - I

LESS THAN 1 VAC

Boiler Monitor

TB3 -3 - I

LESS THAN 0.5 VAC

FROM: BOILER MONITOR to SYSTEM CONTROL

Boiler Monitor

System Control

Indication

TB1 - 1

TB1 - 1

LESS THAN 0.5 VAC

TB1 - 2

TB1 - 2

LESS THAN 0.5 VAC

TB1 - 3

TB1 - 3

LESS THAN 0.5 VAC

TB1 - 2

TB1 - 3

LESS THAN 0.5 VAC