Raypak B6000 User Manual
Page 21

Page 21
SYSTEM CONTROL/DISPLAY FAMILIARIZATION
The System is set up by using the selector buttons and the displays on the System Control
module.
There are ten or more displays. Each display provides information regarding the system
operating parameters and system component status. Some displays provide information
only, such as current outdoor temperature, system temperature, etc..
Selectable data is identified by flashing characters.
The selector buttons are:
"MENU" - which when pressed will change displays.
"SELECT" - moves the cursor - flashing character - to the next selection in a display.
"+" - moves a value to a higher reading (e.g. Display shows flashing boiler #1. Pushing
"+" will change display to boiler #2).
"–" - moves a value to a lower position (e.g. Display shows flashing boiler #2. Pushing
"–" will change display to boiler #1).
EDITING B6000 DISPLAYS LOCATION
The B6000 BMS has a forty (40) character screen that displays status and memory contents.
Selectable Parameters on the B6000 Monitor Screen are as follows:
Selectable Parameters
Range
Value
Change to Fahrenheit (F) or Celsius (C).
Default (After Initialization)
Maximum Water Temp
70 - 235
Degrees…………180
Set
40 - 220
Degrees…………100
Day Temperature
40 - 220
Degrees…………100
Nite
40 - 220
Degrees………… 90
Ratio
None - 20:1
Numeric…………1.0:1
° Rise
1 - 99
Degrees………… 20
Step
1s,2s, 5 - 100
Percentile……… 20
O/C (Outdoor Cutoff)
35 - 199
Degrees………… 65
O/Cdb (O/C dead band)
1 - 9
Degrees………… 4
CBand (Control Band)
1 - 9
Degrees………… 3
Lead
1 - 8
Numeric………… 1
Change Hours
0 - 225
Numeric…………100
Pump Delay *
0 - 20
Minutes………… 3
Ign Time*
15 - 100
Seconds………… 30
*Indicates multiple entries
When the B6000 BMS is equipped with a night setback feature, [ WHEN INITIALIZED],
NITE SETBACK defaults to OFF.