beautypg.com

Installation, Installation codes, Equipment base – Raypak 500 User Manual

Page 8: Clearances

background image

Clearances

Indoor Installations

When installed according to the listed minimum clear-

ances from combustible construction, these heaters

can be serviced without removing permanent structur-

al construction around the heater. However, for ease

of servicing, we recommend a clearance of at least 24

in. in front, at least 24 in. on the rear and 24 in. above

the top of the heater. This will allow the heater to be

serviced in its installed location without movement or

removal of the heater.

Service clearances less than the minimum may

require removal of the heater to service either the heat

exchanger or the burner components. In either case,

the heater must be installed in a manner that will

enable the heater to be serviced without removing any

structure around the heater.

Outdoor Installations

These heaters are design-certified for outdoor installa-

tion. Heaters must not be installed under an overhang

unless clearances are in accordance with local instal-

lation codes and the requirements of the gas supplier.

Three sides must be open in the area under the over-

hang. Roof water drainage must be diverted away

from heaters installed under overhangs.

Equipment Base

The heater must be mounted on a level, structurally

sound surface. The heater is approved for installation

on a combustible surface but must NEVER be

installed on carpeting. Gas-fueled equipment installed

in enclosed parking garages must be located at least

18 in. above the floor.

In addition, the heater shall be installed such that the

gas ignition system components are protected from

water (dripping, spraying, rain, etc.) during appliance

operation or service (circulator replacement, control

replacement, etc.).

If the heater needs to be secured to the ground, use

the holes in the anchoring legs on the heater.

8

Table D: Clearances — Indoor Installations

INSTALLATION

Installation Codes

Installations must follow these codes:

Local, state, provincial, and national codes, laws,

regulations and ordinances

National Fuel Gas Code, ANSI Z223.1/NFPA 54 –

latest edition (NFGC)

National Electrical Code, ANSI/NFPA 70 - latest

edition (NEC)

Standard for Controls and Safety Devices for

Automatically Fired Boilers, ANSI/ASME CSD-1,

(CSD-1) when required

For Canada only: CAN/CSA B149 Natural Gas

and Propane Installation Code and CSA C22.1

C.E.C. Part 1 (C22.1)

*DO NOT install on carpeting.

CAUTION: This boiler should be located in an area

where water leakage will not result in damage to the

area adjacent to the appliances or to the structure.

When such locations cannot be avoided, it is

recommended that a suitable catch pan, adequately

drained, be installed under the appliance. The pan

must not restrict air flow.

Heater

Side

Min. Clearances

from Combustible

Surfaces

Recommended

Service

Clearances

Floor*

0”

0”

Rear

24”

24”

Right Side

0”

0”

Left Side

0”

0”

Top

12”

24”

Front

Open

24”

Vent

1”

1”

CAUTION: The boiler must be level to allow

condensate to drain properly from the heat

exchanger.

This manual is related to the following products: