Sensor resistance values – Raypak 500 User Manual
Page 48
48
1/4”
NOTE: If receiving a NO FLAME F09 fault code, check the gap
spacing between points on the electrode by holding two quarters
together and sliding them through the gap. There should be a slight
resistance.
Fig. 36: Direct Spark Igniter
Temperature Sensors
Water Temperature (°F)
Resistance (ohms)
32
32550
41
25340
50
19870
59
15700
68
12490
77
10000
86
8059
95
6535
104
5330
113
4372
122
3605
131
2989
140
2490
149
2084
158
1753
167
1481
176
1256
185
1070
194
915
203
786
212
667
Outdoor Sensor
Water Temperature (°F)
Resistance (ohms)
–22
171800
–13
129800
–4
98930
5
76020
14
58880
23
45950
32
36130
41
28600
50
22800
59
18300
68
14770
77
12000
86
9804
95
8054
104
6652
113
5522
Sensor Resistance Values